Longitudinal and Source-to-Tap New Orleans, LA, U.S.A. Drinking

The two municipal drinking water systems of New Orleans, LA, U.S.A. were sampled to compare the microbiology of independent systems that treat the sam...
1 downloads 0 Views 529KB Size
Subscriber access provided by University of Newcastle, Australia

Article

Longitudinal and Source-to-Tap New Orleans, LA, USA Drinking Water Microbiology Natalie Marie Hull, Eric P Holinger, Kimberly A Ross, Charles E Robertson, J. Kirk Harris, Mark J Stevens, and Norman R. Pace Environ. Sci. Technol., Just Accepted Manuscript • DOI: 10.1021/acs.est.6b06064 • Publication Date (Web): 15 Mar 2017 Downloaded from http://pubs.acs.org on March 16, 2017

Just Accepted “Just Accepted” manuscripts have been peer-reviewed and accepted for publication. They are posted online prior to technical editing, formatting for publication and author proofing. The American Chemical Society provides “Just Accepted” as a free service to the research community to expedite the dissemination of scientific material as soon as possible after acceptance. “Just Accepted” manuscripts appear in full in PDF format accompanied by an HTML abstract. “Just Accepted” manuscripts have been fully peer reviewed, but should not be considered the official version of record. They are accessible to all readers and citable by the Digital Object Identifier (DOI®). “Just Accepted” is an optional service offered to authors. Therefore, the “Just Accepted” Web site may not include all articles that will be published in the journal. After a manuscript is technically edited and formatted, it will be removed from the “Just Accepted” Web site and published as an ASAP article. Note that technical editing may introduce minor changes to the manuscript text and/or graphics which could affect content, and all legal disclaimers and ethical guidelines that apply to the journal pertain. ACS cannot be held responsible for errors or consequences arising from the use of information contained in these “Just Accepted” manuscripts.

Environmental Science & Technology is published by the American Chemical Society. 1155 Sixteenth Street N.W., Washington, DC 20036 Published by American Chemical Society. Copyright © American Chemical Society. However, no copyright claim is made to original U.S. Government works, or works produced by employees of any Commonwealth realm Crown government in the course of their duties.

Page 1 of 29

Environmental Science & Technology

1

Longitudinal and Source-to-Tap New Orleans, LA, USA Drinking

2

Water Microbiology

3

Natalie M. Hull1*, Eric P. Holinger2, Kimberly A. Ross2, Charles E. Robertson3, J. Kirk Harris4,

4

Mark J. Stevens4, and Norman R. Pace2§

5 6

1 Department of Civil, Environmental, and Architectural Engineering, University of Colorado,

7 8

Boulder, CO 80303, USA 2 Department of Molecular, Cellular, and Developmental Biology, University of Colorado,

9 10

Boulder, CO, 80309, USA 3 Division of Infectious Disease, University of Colorado School of Medicine, Anschutz Campus,

11 12

Aurora, CO, 80045, USA 4 Department of Pediatrics, University of Colorado School of Medicine, Anschutz Campus,

13

Aurora, CO, 80045, USA

14 15

* [email protected]

16

§

[email protected]

ACS Paragon Plus Environment

1

Environmental Science & Technology

17

Page 2 of 29

KEYWORDS

18 19

Drinking water, V1/V2 region 16S rRNA amplicon sequencing, chloramine disinfection

20 21

GRAPHICAL ABSTRACT

22

ACS Paragon Plus Environment

2

Page 3 of 29

23

Environmental Science & Technology

ABSTRACT

24 25

The two municipal drinking water systems of New Orleans, LA, USA were sampled to

26

compare microbiology of independent systems that treat the same surface water from the

27

Mississippi River. To better understand temporal trends and sources of microbiology delivered to

28

taps, these treatment plants and distribution systems were subjected to source-to-tap sampling over

29

four years. Both plants employ traditional treatment by chloramination, applied during or after

30

settling, followed by filtration before distribution in a warm, low water age system. Longitudinal

31

samples indicated microbiology to have stability both spatially and temporally, and between

32

treatment plants and distribution systems. Disinfection had the greatest impact on microbial

33

composition, which was further refined by filtration and influenced by distribution and premise

34

plumbing. Actinobacteria spp. exhibited trends with treatment. In particular, Mycobacterium spp.,

35

very low in finished waters, occurred idiosyncratically at high levels in some tap waters, indicating

36

distribution and/or premise plumbing as main contributors of mycobacteria. Legionella spp.,

37

another genus containing potential opportunistic pathogens, also occurred ubiquitously. Source

38

water microbiology was most divergent from tap water, and each step of treatment brought samples

39

more closely similar to tap waters.

ACS Paragon Plus Environment

3

Environmental Science & Technology

40

Page 4 of 29

INTRODUCTION

41 42

The near sea-level topography of New Orleans, LA presents a unique situation for control

43

of storm water, wastewater, and drinking water, especially when faced with major storm events.

44

The Sewerage and Water Board of New Orleans operates two DWTPs that serve New Orleans

45

parish and parts of surrounding parishes. These plants continuously provide drinking water that

46

meets EPA requirements despite challenging conditions presented by water loss and unresolved

47

damage to buried infrastructure1,2. In 2013, 73% of 56 billion gallons pumped was not metered1,3,

48

demonstrating the magnitude of the battle against storm-induced damage and aging infrastructure

49

in systems with components ranging from 20 to more than 100 years old.

50

A 2011 survey of drinking water microbiology in the southeastern U.S. found that the

51

microbiology of New Orleans, LA drinking water distribution systems (DWDS) differed from that

52

of other communities surveyed, delivering higher relative abundances of phylotypes indicative of

53

fresh and saltwater infiltration (e.g. Planctomycetes and Bacteroidetes) and potential opportunistic

54

pathogens (OPs) (e.g. Legionella and Mycobacterium spp.)4. To potentially elucidate the sources

55

of such microbes and improve understanding of their variation over time, a longitudinal census

56

was conducted on DWDS waters from source, through the drinking water treatment plants

57

(DWTPs), to tap.

58

Recent, culture-independent studies of DWTP and DWDS microbial communities based

59

on gene sequences have provided initial comprehensive assessments of drinking water

60

microbiology. Emerging generalities indicate that Alpha-, Beta- and Gamma-Proteobacteria,

61

Actinobacteria (including Mycobacterium spp.), Cyanobacteria (including non-photosynthetic

62

Melainabacteria5), Methylobacterium spp., and sphingomonads tend to dominate these bacterial

63

assemblages4,6–15. The most studied factor for determining tap water microbiology has been

64

disinfectant choice, mainly chlorine vs. chloramine. Both these disinfectants select for chlorine

65

resistant genes16 and potential opportunistic pathogens (OPs) such as Legionella spp. (for chlorine)

66

and Mycobacterium spp. (for chloramine)8,14,15,17–20. Chlorine disinfection has been shown to

67

reduce relative abundance of Beta-Proteabacteria6,21 and to select for Escherichia-Shigella spp.4,

68

and chloramination has been shown to enrich nitrogen metabolizing organisms11.

69

Proteobacterial assemblages additionally have been shown to shift in response to chlorine

70

residual14, the collective treatment processes16, and pH7. Other water quality parameters, including

ACS Paragon Plus Environment

4

Page 5 of 29

Environmental Science & Technology

71

water age and dissolved oxygen, can also influence microbial composition12. Source water

72

microbiology can be more variable over time than that of finished and DWDS waters 9. Finally,

73

one study sought to identify the origination of the core microbiome of a DWDS within in the

74

DWTP and found that filtration, when performed prior to chloramination, was the major factor

75

determining DWDS community structure7.

76

Aside from accumulation of a census, these and other sequence-based studies highlight the

77

importance and widespread impact of microbial issues facing modern DWTPs and DWDSs10.

78

Public health concerns include OPs22–27, the role of biofilms28 and amoebae25,29,30 in OP survival

79

and proliferation in DWDSs, the selection for and harboring of antibiotic resistance31–33, and water

80

quality impacts such as nitrification4,13,34 and microbial corrosion35. The investigation presented

81

here of the origination and distribution of microbes in New Orleans DWTPs and DWDSs

82

contributes to an essential knowledge base for better understanding and control of the

83

microbiology of public drinking water systems. The specific goals of the research were to improve

84

understanding of the New Orleans water system microbiota; over time, from source to tap, and

85

comparatively between systems.

86 87

METHODS

88 89

New Orleans, DWTPs and DWDSs

90 91

These two DWTPs present a rare opportunity to systematically and longitudinally compare

92

independent systems treating the same water from the Mississippi River, from source to tap. The

93

Carrolton DWTP produces 135 mgd (design capacity = 232 mgd) and serves the East Bank of the

94

Mississippi River, while the Algiers DWTP produces 11 mgd (design capacity = 40 mgd) and

95

serves the residential West Bank.

96

coagulation, flocculation, and sedimentation of raw water and return sediments to the river1.

97

Disinfection by sodium hypochlorite followed by anhydrous ammonia (to produce chloramine)

98

occurs simultaneously in the upflow clarifier at Algiers, but in contact basin subsequent to the

99

settling basin at Carrolton1. After pH adjustment with lime, fluoridation with fluorosilicic acid,

100

and calcium sequestration with polyphosphate, disinfected water at both plants is rapidly filtered

Both plants add polyelectrolyte and ferric sulfate for

ACS Paragon Plus Environment

5

Environmental Science & Technology

Page 6 of 29

101

through sand and anthracite before distribution1. Pipe materials include cast iron, cement, and

102

PVC, and some are above ground. Both systems have elevated storage tanks.

103 104

Study Design

105 106

In the published 2011 study that prompted return to New Orleans4, 13 tap samples served

107

by Carrolton DWTP and 1 raw sample from the Mississippi River were collected. The 2012

108

campaign sampled taps representing the spatial extent of both Carrolton and Algiers DWDSs,

109

finished (exiting the filters prior to distribution) waters, and raw waters for both DWTPs. In 2012,

110

samples collected included 2 raw water samples at each DWTP river intake, 3 Algiers and 2

111

Carrolton finished water samples, and 6 Algiers and 35 Carrolton tap water samples. To sample

112

each step in each DWTP in 2014, filter media core samples, 1 raw water sample at each DWTP

113

river intake, 2 Carrolton settling basin samples, 2 post- disinfection samples for each DWTP, 6

114

Algiers and 28 Carrolton finished water samples, and 6 tap water samples taken from hose bibs

115

coinciding with monitoring compliance locations for each DWDS were collected. All sampling

116

campaigns were conducted in spring, representing a midpoint for the temperature range in this

117

warm climate. For the taps sampled and representing the spatial extent of the distribution system,

118

the estimated water age is < 1.5 days at Carrolton and < 2 days at Algiers. Location of taps, raw

119

water intake, and each DWTP are indicated in Figure 1.

120

ACS Paragon Plus Environment

6

Page 7 of 29

Environmental Science & Technology

121 122

Figure 1: Map indicating New Orleans, LA water taps sampled in 2011 (red circles), 2012 (blue

123

circles), and 2014 (green circles); raw Mississippi river intakes (black triangles) for Algiers and

124

Carrolton DWTPs (black squares); and the Mississippi river water sampled in 2011 (white

125

triangle). World Light Gray Canvas Base map was downloaded from ArcGIS Online, and

126

contributors included Esri, HERE, DeLorme, MapmyIndia, © OpenStreetMap contributors, and

127

the GIS user community.

128 129

Sample Collection and Processing

130 131

Water Samples: After flushing premise plumbing water from the cold tap as measured by

132

temperature stabilization, the Hanna HI-9828 multiprobe (Hanna Instruments, Woonsocket, RI)

133

was used to collect temperature (Temp, °C), salinity (mg/g), dissolved oxygen (DO, mg/L), total

134

dissolved solids (TDS, mg/L), conductivity (Cond, µS/cm), and pH data. Total chlorine (Tot Cl,

135

mg/L) was measured on the Hanna HI 96711 Photometer (using HI 93711-0 reagent) by

136

manufacturer’s instructions. At each tap, 1.5 - 2 L of water was collected in sterile Nalgene high-

137

density polyethylene (HDPE) bottles after one tap-water rinse. Samples were stored on ice until

138

sterile 0.2 µm polycarbonate filtration and freezing of filters within 12 hours. All other water

139

samples were collected following the same protocol, at designated DWTP ports. In 2014, river

140

samples were collected at each DWTP treatment plant intake using a custom weighted metal

ACS Paragon Plus Environment

7

Environmental Science & Technology

Page 8 of 29

141

holster after one rinse by submersion of the sampling vessel in the river. The 2011 river sample

142

was collected between DWTP intakes4 but was not re-sequenced for source-to-tap comparison due

143

to location difference.

144 145

Filter Media Samples: Filters consist of a silt layer that gradually accumulates over 6

146

inches of anthracite, followed by 18 inches of sand, supported by 5 graduated layers of gravel.

147

Filters were backwashed weekly for ~30 minutes with finished water from an elevated storage

148

tank (used only for backwash at Carrolton) until water ran clear (with air scouring midway through

149

cleaning at Algiers). Media samples were collected using a 70% ethanol-cleaned hinged 2 inch

150

diameter metal coring device. Each filter bed was drained immediately before collection at 3 inch

151

intervals along the top ~12 inches of filter depth of 15 mL of media from: top silt layer (A), top of

152

anthracite below silt layer (B), bottom of anthracite above sand layer (C), and sand layer (D), and

153

stored on ice until freezing within 12 hours. For one Algiers filter, 2 A, 1 B, 1 C, and 1 D samples

154

were collected. For two Carrolton filters, 6 A, 3 B, 3 C, and 3 D samples were collected.

155 156

DNA Extraction and Quantitation

157 158

Genomic DNA was purified from water samples by phenol:chloroform extraction and

159

bead-beating of thawed polycarbonate filters, with final suspension in 40 µL TE (10 mM Tris, pH

160

8.0, 1 mM EDTA), as described previously36. Similarly, a known mass (~0.5 g) of wet filter media

161

was extracted from each sample by weighing extraction tubes before and after adding vortex-

162

homogenized filter media. Triplicate qPCR reactions were used to estimate total bacterial DNA

163

in sample extracts as described previously37, and normalized to water sample volume or filter

164

media mass.

165 166

16S Amplicon Library Construction and Sequencing

167 168

Bacterial profiles were determined by amplification and analysis of 16S rRNA gene

169

sequences as described previously36,38,39. Amplicons were generated using 27F and 338R primers

170

targeting ~300 base pairs of the bacterial V1/V2 variable region. PCR products were normalized

171

by gel densitometry, and pooled, purified, and concentrated using a DNA Clean and Concentrator

ACS Paragon Plus Environment

8

Page 9 of 29

Environmental Science & Technology

172

Kit (Zymo, Irvine, CA). Pooled amplicons were quantified by Qubit Fluorometer 2.0 (Invitrogen,

173

Carlsbad, CA), diluted to 4nM, and denatured with 0.2 N NaOH at room temperature. Denatured

174

DNA was diluted to 15pM, spiked with 25% Illumina PhiX control DNA, and sequenced by

175

Illumina paired-end sequencing on the MiSeq platform (MiSeq Control Software v2.2.0.2, MiSeq

176

Reporter v2.2.29, 500 cycle v2 reagent kit). The 2011 river and tap samples were previously

177

sequenced by 454 pyrosequencing4, but tap samples were re-sequenced by Illumina MiSeq for this

178

study to eliminate potential sequencing technology bias.

179 180

Taxonomic Analysis of Paired-end Sequences

181 182

As previously described39, sequences were sorted by sample via barcodes in the paired

183

reads with a python script. After removing barcode, linker, and primers, sequences were deposited

184

in the NCBI Short Read Archive under accession numbers SRP079986, SRP079990, and

185

SRP086804 for 2011, 2012, and 2014 libraries. Deposited sequences were assembled using

186

phrap40,41, discarding pairs that did not assemble. Assembled sequences were trimmed over a

187

moving window of 5 nucleotides until average quality met or exceeded 20, discarding sequences

188

with more than 1 ambiguity or shorter than 200 nucleotides (nt). Potential chimeras were identified

189

with Uchime42 (usearch6.0.203_i86linux32) using the Schloss Silva reference sequences43 and

190

discarded. Resulting sequences were aligned and classified with SINA44 (1.2.11) using the

191

bacterial sequences in Silva 111Ref45 as reference, configured to yield the Silva taxonomy.

192

Operational taxonomic units (OTUs) were produced by clustering sequences with identical

193

taxonomic assignments.

194 195

Microbial Community Analysis

196 197

Removal of singleton, doubleton, chloroplast, and unclassified sequences left 6,072,331

198

bacterial sequences for 146 libraries from the three sequencing runs encompassing 2011, 2012,

199

and 2014 samples. Average library size was 41,311 sequences of 250 nt average length per sample.

200

In addition to Microsoft Excel 2013 (used for t-tests), the software package Explicet46 (v2.10.5,

201

www.explicet.org) was used for data exploration, manipulation, and calculation of ShannonH

202

alpha diversity at rarefaction, calculation of Morisita-Horn beta diversity at rarefaction using

ACS Paragon Plus Environment

9

Environmental Science & Technology

Page 10 of 29

203

average relative abundances for sample groups, and calculation of two-part analysis p-values

204

adjusted for multiple sample comparisons within groups47. At rarefaction, Good’s coverage was

205

>99%. The vegan package48 (v2.3-5) in R49 (v3.3.0) using RStudio50 (v0.99.902) was used to plot

206

an ordination of 69 source-to-tap libraries in the 2014 dataset. A Bray-Curtis distance matrix was

207

calculated on the rarefied (to minimum library size of 11,458 sequences/sample) and Hellinger-

208

transformed (to normalize variance) OTU table, and plotted in a 2-dimensional Non-Metric

209

Multidimensional Scaling (NMDS)51,52 ordination, where the proximity of samples represents their

210

compositional similarity. Modeled fit was assessed by stress and Shepard plot51.

211 212

RESULTS

213 214

Water Quality

215 216

Water quality parameters that could impact microbiology were measured over time from

217

source to tap during each sampling campaign and averages are summarized in Table 1.

218

Longitudinally, total chlorine in finished and tap waters remained constant at ~3 mg/L for

219

Carrolton, but decreased for Algiers between 2012 and 2014. Chlorine residual dropped during

220

distribution by ~0.3 mg/L from finished to tap in both DWDSs in 2012 and 2014 (t-test each year

221

p < 0.05). In general, tap and finished water had higher pH, conductivity, total dissolved solids,

222

and dissolved oxygen than raw water. Additionally, dissolved oxygen in raw Mississippi River

223

water decreased while temperature increased over time. Routine monitoring data provided by the

224

utility during the sampling campaign indicated river water TOC = 5.9 ppm and DOC = 3.7 ppm,

225

and finished water TOC = 2.3 ppm. Salinity was also higher in finished and tap waters than in raw

226

waters (t-test all samples p < 0.05).

227 228 229 230 231 232 233 234 235 236

ACS Paragon Plus Environment

10

Page 11 of 29

Environmental Science & Technology

237

Table 1: Longitudinal and source-to-tap average water quality parameters + standard deviation for

238

Carrolton (C) and Algiers (A) DWTPs, where Raw = river water, Fin = finished water before

239

entering distribution system, and Tap = water sampled at taps throughout the distribution system.

240 Tot Cl mg/L 2011

2012

Raw Tap Raw Fin Tap

C

2.9 ± 0.3

A C A C

3.3 ± 0.2 3.2 ± 0.1 3.1 ± 0.2 2.9 ± 0.6

A C A C

2.6 ± 0.2 3.1 ± 0.3 2.2 ± 0.8 2.9 ± 0.6

Raw 2014

Fin Tap

DO mg/L

pH

11.3 13.3 ± 1.7 8.8 ± 3.1 8.5 ± 2.8 9.1 ± 3.6 10.7 ± 0.9 10.9 ± 1.9 4.8 ± 0.1 6.5 ± 1.4 6.3 ± 2.4 6 ± 0.8 5.2 ± 0.4

8.2 8.8 ± 0.2 8.2 ± 0.1 9.2 ± 0.1 9.1 ± 0.1 9.4 ± 0 9.2 ± 0.2 8.5 ± 0.2 9.1 ± 0.3 9.1 ± 0.2 9.4 ± 0.4 9.3 ± 0.2

Temp °C

Cond µS/cm

TDS mg/L

Salinity mg/g

16.8 17.3 ± 2.3 16.9 ± 0.9 17.5 ± 1.2 19.3 ± 1.3 21.2 ± 1.9 20.9 ± 0.3 20.6 ± 1.4 21.9 ± 0.8 22.7 ± 1.3 23.8 ± 1.3

319 347 ± 33 290 ± 3 306 ± 6 349 ± 9 317 ± 6 361 ± 21 375 ± 1 350 ± 13 441 ± 27 354 ± 14 449 ± 4

235 264 ± 11 145 ± 2 153 ± 3 174 ± 4 158 ± 3 181 ± 10 188 ± 1 175 ± 7 220 ± 14 177 ± 7 224 ± 2

0.17 0.20 ± 0.01 0.14 ± 0.00 0.15 ± 0.01 0.17 ± 0.01 0.15 ± 0.00 0.17 ± 0.01 0.18 ± 0.00 0.17 ± 0.01 0.21 ± 0.01 0.17 ± 0.01 0.22 ± 0.01

241 242 243

Temporal Trends in DWDS Bacterial Assemblages

244 245

As shown in Figure 2, three phyla (Proteobacteria, Actinobacteria, and Bacteroidetes)

246

dominated microbial assemblages in raw, finished and tap water samples for both systems over

247

the sampling period, representing >93% of overall bacterial relative abundance.

Relative

248

abundances for all taxa in all samples are detailed in Supplementary Figure S1.

Of the

249

Proteobacteria, Betaproteobacteria were most abundant overall (26 % in raw, 18 % in finished,

250

and 16 % in tap waters), while Alphaproteobacteria were more abundant in raw water (11% in

251

raw, 7% each in finished and tap waters), and Gamma-Proteobacteria were more abundant in

252

treated water (5% in raw, 7% in finished, and 11 % in tap waters). Overall relative abundances of

253

Actinobacteria, which include hgcl-clade and CL500-29-marine-group representatives, increased

254

over time in raw water (17% in 2012, 30% in 2012, and 42% in 2014) but remained stable in tap

255

water (~22%). Raw water assemblages had greater alpha-diversity (ShannonH = 5.7 + 0.4, mean

256

+ standard deviation) than treated waters (finished water = 4.8 + 0.4, tap water = 4.7+ 0.8), and

257

were longitudinally consistent in microbiology.

ACS Paragon Plus Environment

11

Environmental Science & Technology

Page 12 of 29

258

Variation in taxon dominance and alpha diversity between finished and tap waters could

259

indicate contributions from premise and distribution pipes, as shown particularly for potential OP

260

Mycobacterium spp. in Figure S2. For example, in 2012 when the most taps were sampled, all

261

finished waters contained 1%

262

mycobacterial sequences, and 20% of taps contained >10% mycobacterial sequences. The spatial

263

distribution of elevated mycobacterial sequences was generally idiosyncratic, suggesting premise

264

plumbing as the main source of enrichment. Only two pairs of closely proximal tap samples with

265

elevated mycobacterial sequences could indicate the possible contribution of localized DWDS

266

enrichment. Though Legionella spp. relative abundances were greater in raw waters, they were

267

found ubiquitously in finished and tap waters at >1% relative abundance, and in more than half

268

the taps at >10% relative abundance (Fig S2). Although potential OP sequence enrichment was

269

observed in many 2011 and 2012 taps, only one tap sample in 2014 contained >1% Mycobacterium

270

and no tap sample contained >10% Legionella spp. sequences. This indicates possible longitudinal

271

turnover of dominant phylotypes in both distribution and premise plumbing. Differences could

272

also be attributed to sampling more broadly from taps in buildings in 2012, versus sampling at

273

compliance monitoring outdoor hose bibs with less indoor plumbing influence in 2014.

274

The most dominant taxa in finished water assemblages generally were longitudinally

275

consistent, though dominance shifted from Arcicella and Legionella spp. in 2012 to CL500-29-

276

marine-group in 2014 (two-part p 9) compared to raw water (~8.3), and variation in conductivity, salinity,

388

and TDS likely resulted from treatment process chemical additions. The high pH and chloramine

389

disinfection are directly comparable to the DWTP studied by Pinto et al7, as were the water

390

temperatures for their spring and fall samples. The increased DO in tap vs. raw water is likely

391

attributable to pressurization of water lines for distribution. Increased temperature over the

392

sampling period could have partially contributed to the substantial decrease in raw water DO. The

393

relatively warm temperature of source and tap water could have contributed to the widespread

394

abundance of particular taxa, for example Legionella spp.53 While these sampling campaigns

ACS Paragon Plus Environment

18

Page 19 of 29

Environmental Science & Technology

395

indicate the long term stability of these systems by sampling each spring over the course of several

396

years, potential seasonal variations were not measured. The annual reproducibility correlates with

397

the yearly stability observed in tap microbiota by Pinto et al., where seasonal variations were

398

observed7,9.

399 400

Actinobacteria Gradients

401 402

Detection of Actinobacteria, most commonly Mycobacterium spp., in DWTP and DWDS

403

studies (especially in treated waters) has been reported frequently4,11,14,32,54. In New Orleans, raw

404

river water was most abundant in hgcl-clade Actinobacteria, a group of freshwater and estuarine

405

organisms55–61. On the other hand, representatives of the CL500-29-marine-group of marine and

406

estuarine Actinobacteria56,62,63 were enriched in finished and tap waters in New Orleans (Figure

407

2), particularly by filtration and disinfection (Figure 3). Additionally, CL-500-29-marine-group

408

relative abundance increased longitudinally in all sample types (Figure 2). The decrease in hgcl-

409

clade from raw water to taps observed in this study contrasts with another study in which this

410

group was seen to maintain constant relative abundances throughout a DWTP54. This difference

411

could be attributed to differing treatment processes, where a chloraminated treatment train similar

412

to that of New Orleans was applied in parallel to an advanced treatment train additionally

413

incorporating ozone and GAC. Stratification of hgcl and CL500-29 clades in filter media could be

414

partially explained by their susceptibility to changes in DOM, where decreasing amounts of

415

bacterial DNA with increased filter depth indicate a decline in overall biomass64(Figures 3 and 4).

416

The interplay between actinobacterial representatives may be important for a sea level

417

system like New Orleans with old and damaged pipes that undergo frequent repair, where there

418

are relationships between environmental (hgcl-clade and CL-500-29-marine-group) and potential

419

OP (Mycobacterium spp.) taxa. For example, an indirect longitudinal correlation occurs for

420

relative abundances of Mycobacterium spp. and CL500-marine-group in raw, finished, and tap

421

waters.

422

Mycobacterium spp. relative abundances consistently increased from source to tap in 2012 and

423

2014, in agreement with another study showing selection for such potential OPs by treatment54.

424

Though coastal DWDS’s may battle similar marine intrusions, and all systems battle leaks and

Additionally, although bacterial DNA decreased from source to tap (Figure 4),

ACS Paragon Plus Environment

19

Environmental Science & Technology

Page 20 of 29

425

infiltration, specific interactions between microbial communities in pipes and the environment

426

may differ in other soils, climates, and in freshwater.

427 428

Source Water and Distribution System Shape Core Microbiology

429 430

Several aquatic and soil associated microbes were present in raw river water and eventually

431

constituted the fairly stable finished and tap water microbiomes, including marine groups,

432

freshwater groups, hgcl clade spp., Sediminibacterium spp., Limnohabitans spp., Arcicella spp.

433

and others. The persistence of these environmental groups in finished and tap waters presumably

434

reflects a high degree of selection for these taxa by treatment. Additionally, the occurrence of

435

some environmental groups could result from infiltration during distribution, or seeding of pipe

436

microbiology during frequent repair and flooding events. The low water age (