Effect of disinfectant exposure on Legionella pneumophila associated with simulated drinking water biofilms: release, inactivation, and infectivity Yun Shen, Conghui Huang, Jie Lin, Wenjing Wu, Nicholas J. Ashbolt, Wen-Tso Liu, and Thanh H. Nguyen Environ. Sci. Technol., Just Accepted Manuscript • DOI: 10.1021/acs.est.6b04754 • Publication Date (Web): 13 Jan 2017 Downloaded from http://pubs.acs.org on January 15, 2017
Just Accepted “Just Accepted” manuscripts have been peer-reviewed and accepted for publication. They are posted online prior to technical editing, formatting for publication and author proofing. The American Chemical Society provides “Just Accepted” as a free service to the research community to expedite the dissemination of scientific material as soon as possible after acceptance. “Just Accepted” manuscripts appear in full in PDF format accompanied by an HTML abstract. “Just Accepted” manuscripts have been fully peer reviewed, but should not be considered the official version of record. They are accessible to all readers and citable by the Digital Object Identifier (DOI®). “Just Accepted” is an optional service offered to authors. Therefore, the “Just Accepted” Web site may not include all articles that will be published in the journal. After a manuscript is technically edited and formatted, it will be removed from the “Just Accepted” Web site and published as an ASAP article. Note that technical editing may introduce minor changes to the manuscript text and/or graphics which could affect content, and all legal disclaimers
Environmental Science & Technology is published by the American Chemical Society. 1155 Sixteenth Street N.W., Washington, DC 20036 Published by American Chemical Society. Copyright © American Chemical Society. However, no copyright claim is made to original U.S. Government works, or works produced by employees of any Commonwealth realm Crown government in the course of their duties.
Subscriber access provided by UNIV OF CALIFORNIA SAN DIEGO LIBRARIES
and ethical guidelines that apply to the journal pertain. ACS cannot be held responsible for errors or consequences arising from the use of information contained in these “Just Accepted” manuscripts.
Environmental Science & Technology is published by the American Chemical Society. 1155 Sixteenth Street N.W., Washington, DC 20036 Published by American Chemical Society. Copyright © American Chemical Society. However, no copyright claim is made to original U.S. Government works, or works produced by employees of any Commonwealth realm Crown government in the course of their duties.
Page 1 of 32
Environmental Science & Technology
Biofilms developed under disinfectant exposure Stiff
Biofilms developed under disinfectant lacking condition Biofilm Development
Soft
L. pneumophila Associated with Biofilms Disinfectant Flush
L. pneumophila Released from Biofilms under Flow
Disinfectant Flush
Released L. pneumophila: Lower inactivation and higher infectivity
Released L. pneumophila: Higher inactivation and lower infectivity ACS Paragon Plus Environment
Environmental Science & Technology
1
Effect of disinfectant exposure on Legionella pneumophila associated with simulated
2
drinking water biofilms: release, inactivation, and infectivity
3 4
Yun Shen1*, Conghui Huang1, Jie Lin1, Wenjing Wu1, Nicholas J. Ashbolt2, Wen-Tso Liu1,
5
Thanh H. Nguyen1
6
1
7
2
Department of Civil and Environmental Engineering, University of Illinois at Urbana-Champaign, School of Public Health, University of Alberta, AB T6G 2G7 Canada.
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
* Present Address: 1351 Beal Ave., 219 EWRE Bldg. Ann Arbor, MI 48109-2125. Phone: +1 (217) 898 1087. Email:
[email protected] 31 1 ACS Paragon Plus Environment
Page 2 of 32
Page 3 of 32
Environmental Science & Technology
32
Abstract
33
Legionella pneumophila, the most commonly identified causative agent in drinking water
34
associated with disease outbreaks, can be harbored by and released from drinking water
35
biofilms. In this study, the release of biofilm-associated L. pneumophila under simulated
36
drinking water flow containing a disinfectant residual was examined. Meanwhile, the
37
inactivation and infectivity (to amoebae) of the released L. pneumophila were studied. To
38
simulate drinking water system conditions, biofilms were prepared under either
39
disinfectant exposure (pre-disinfected biofilms) or disinfectant-free (untreated biofilms)
40
conditions, respectively. For experiments with water flow containing a disinfectant to
41
release the biofilm-associated L. pneumophila from these two types of biofilms, the L.
42
pneumophila release kinetics from pre-disinfected and untreated biofilms under flow
43
condition were not statistically different (One-way ANOVA, p>0.05). However,
44
inactivation of the L. pneumophila released from pre-disinfected biofilms was 1-2 times
45
higher and amoeba infectivity was 2-29 times lower than that from untreated biofilms. The
46
higher disinfectant resistance of L. pneumophila released from untreated biofilms was
47
presumably influenced by the detachment of a larger amount of biofilm material
48
(determined by 16S rRNA qPCR) surrounding the released L. pneumophila. This study
49
highlights the interaction among disinfectant residual, biofilms, and L. pneumophila, which
50
provides guidelines to assess and control pathogen risk.
51
2 ACS Paragon Plus Environment
Environmental Science & Technology
52
Introduction
53
From 2014-2015, a serious Legionnaires’ disease outbreak occurred in Flint, MI, causing
54
87 illness cases and 11 deaths (data collected from June 2014 to March 2015 and May 2015
55
to October 2015).1 At the same time, Legionella pneumophila, the causative agent of
56
Legionnaires’ disease, was detected in half of the 60 premise plumbing water samples
57
collected at two hospitals in Flint.2 Although the link between L. pneumophila in drinking
58
water and the Legionnaires’ outbreak has not been identified yet in Flint, L. pneumophila
59
was the most commonly reported pathogen causing drinking water disease outbreaks in the
60
United States.3-6 From 2011 to 2012, L. pneumophila led to 21 drinking water outbreaks,
61
contributing to 66% of the total reported disease outbreaks associated with drinking water
62
in the United States.6 Although disinfectant residual is required in most drinking water
63
systems by the U.S. Environmental Protection Agency (USEPA), L. pneumophila is known
64
to be more resistant to disinfectants when associated with drinking water biofilms.7-13
65
Biofilms in drinking water distribution or premise plumbing systems can accumulate L.
66
pneumophila and provide nutrients for its growth.12,
67
pneumophila cells can be protected from disinfection because biofilm extracellular
68
polymeric substance (EPS) consumes disinfectant and reduces disinfectant permeation.9, 15
69
Subsequently, L. pneumophila cells may be released to the drinking water with sloughed
70
off biofilms and reach consumers. Therefore, biofilm protection and the efficacy of
71
disinfectants are two key factors determining the health risk of L. pneumophila released
72
into drinking water. Furthermore, mechanistic understanding of the interactions among
73
biofilms, disinfectants, and L. pneumophila is critical for developing Legionnaires’ disease
74
control strategies.
14
These biofilm-associated L.
3 ACS Paragon Plus Environment
Page 4 of 32
Page 5 of 32
Environmental Science & Technology
75
Biofilm microbial composition and disinfectant types were reported to influence the
76
disinfection efficacy of biofilm-associated L. pneumophila and other pathogens.16-22 For
77
example, biofilms composed by single species (Microbacterium phyllosphaerae or L.
78
pneumophila) were shown to be less tolerant to hydrogen peroxide or dendrimer exposure
79
than mixed-species biofilms.21,
80
distribution systems (DWDS) could shift their community composition to resist
81
disinfectant exposure23,
82
pathogens. Also, compared to free chlorine, monochloramine had slower reactivity but
83
diffused deeper into biofilms, thus monochloramine could provide better biofilm
84
disinfection efficiency.19,
85
associated pathogen disinfection under quiescent conditions,16-22 ignoring possible effects
86
associated with drinking water flow conditions. Flow is an important consideration for
87
biofilm-associated pathogens disinfection, as shear stress brings disinfectants to the biofilm
88
surface and may enhance the flux of disinfectants into biofilms.25 Meanwhile, shear stress
89
may lead to higher release of biofilm-associated pathogens.14 Overall, disinfection efficacy
90
during concurrent release of biofilm-associated pathogens under continuous flow
91
conditions appears to be unreported. Moreover, in a real drinking water system, non-
92
uniform exposure of biofilms to disinfectants may exist because of disinfectant
93
consumption (by the biomass, natural organic matter, or pipe corrosion materials), altered
94
temporal and spatial flow rate, and different water system operation. Furthermore, biofilms
95
grown under different disinfectant exposure conditions could have different chemical
96
compositions and mechanical properties, providing variation in the protection of biofilm-
97
associated pathogens.26-28 How disinfectant residual exposure during biofilm development
24
20
22
These mixed-species biofilms in drinking water
and thus maintain their protection for biofilm-associated
These previous studies have largely investigated biofilm-
4 ACS Paragon Plus Environment
Environmental Science & Technology
98
influences the subsequent biofilm-associated pathogen release and disinfection is also
99
unknown. What is known, however, is that planktonic L. pneumophila cells were still able
100
to infect Acanthamoeba castellanii four months after the commencement of
101
monochloramine treatment.29 Yet the infectivity of released biofilm-associated pathogens
102
in the presence of residual disinfectants is poorly documented and confounded by methods
103
available to detect viable versus active cells.30
104
Here we present a comprehensive study to understand the interactions among biofilms,
105
disinfectants (free chlorine vs. monochloramine), and L. pneumophila. The biofilms used
106
in this study were developed under simulated DWDS conditions in the presence or absence
107
of a disinfectant residual. The L. pneumophila release process in drinking water systems
108
was simulated by continuously flowing the water containing disinfectant over the biofilms
109
harbored with L. pneumophila. The released samples were then collected for further
110
analysis of L. pneumophila release kinetics, inactivation, and infectivity. The effect of pre-
111
disinfecting biofilms and disinfectant types was then identified, accordingly. The results of
112
this study will provide guidelines to assess the potential health risks of L. pneumophila in
113
drinking water.
114
Materials and Methods
115
Biofilm preparation
116
Biofilms used in this study were developed from sand filtered groundwater, a source of
117
drinking water in Urbana–Champaign, IL. This groundwater source has pH of 7.5 and
118
hardness of 280 mg/L. The metals, TOC, and TDS in this groundwater source were shown
119
in the Supporting Information (SI, Table S1). To remove excessive mineral precipitates
5 ACS Paragon Plus Environment
Page 6 of 32
Page 7 of 32
Environmental Science & Technology
120
formed when the groundwater was exposed to air, the groundwater was pre-treated by sand
121
filtration. As described previously,14, 31 this groundwater was continuously introduced into
122
CDC reactors (CBR 90-2, BioSurface Technologies Corporation, Bozeman, MT) that were
123
stirring at 125 rpm or a Reynold number of 2384, so as to develop biofilms on PVC coupons
124
(RD 128-PVC, BioSurface Technologies Corporation, Bozeman, MT). No external
125
bacteria or nutrients were intentionally added to the CDC reactors. The biofilms were
126
grown in the CDC reactor for one year before disinfection. The one-year old biofilms had
127
the thickness of 120±8 m.26
128
After one year of growing biofilms with disinfectant-free groundwater, PVC biofilm
129
coupons were then distributed across three CDC reactors for a further six months of
130
disinfectant/disinfectant-free exposure (Figure 1). Specifically, groundwater amended with
131
monochloramine or free chlorine (4 mg Cl2·L-1) was continuously introduced to Reactors
132
1 and 2, respectively. The pH of disinfectant-containing groundwater was 7.5. The total
133
chlorine and free chlorine concentration was determined by a DR 2700™ Portable
134
Spectrophotometer according to the DPD colorimetric method (Standard Method 4500-Cl
135
G). Reactor 3 was only exposed to the disinfectant-free groundwater. Reactors 1 and 2 were
136
used to simulate high disinfectant exposure conditions for DWDS, while Reactor 3 was
137
used to simulate the situation when the disinfectant residual was lacking. The feed
138
disinfectant solutions were prepared and replenished every second day. The biofilms from
139
these three reactors were imaged by optical coherence tomography (OCT) and shown in
140
Figure S1. No significant difference in biofilm thickness was observed (p>0.05).
141
Disinfection and release of biofilm-associated L. pneumophila
6 ACS Paragon Plus Environment
Environmental Science & Technology
142
To simulate the association of pathogenic L. pneumophila to drinking water biofilms,
143
L. pneumophila (ATCC 33152) was pre-adhered to monochloramine-treated (Reactor 1),
144
free-chlorine-treated (Reactor 2), and untreated (Reactor 3) biofilms using a parallel plate
145
flow chamber (FC 71, BioSurface Technologies Corporation, MT), as described
146
previously.13 Before each experiment, one biofilm coupon was carefully removed from the
147
CDC reactor and inserted into the flow chamber. Groundwater containing 1–5 × 107
148
cells∙mL-1 of L. pneumophila was then pumped into the flow chamber at an average flow
149
velocity of 0.007 m.s-1 for half an hour. The HRT for the L. pneumophila solution above
150
the biofilm coupon was approximately 2s. These adhered cells were then allowed to
151
incorporate into the biofilms under quiescent flow conditions for two days before the
152
subsequent L. pneumophila release experiments.
153
The process of L. pneumophila release from biofilms by the drinking water flow
154
containing or lacking disinfectant was simulated in the flow chamber to resemble the varied
155
disinfectant residual concentrations. Briefly, the groundwater containing disinfectant or
156
groundwater free of disinfectant was introduced into the flow chamber at a flow velocity
157
of 0.4 m·s-1 to detach the pre-adhered L. pneumophila from the biofilms (Figure 1). This
158
flow velocity is within the range of real drinking water flow velocity.32 Specifically, for
159
the monochloramine-treated biofilms, the adhered L. pneumophila in biofilms was
160
detached by groundwater containing 0.5 mg Cl2·L-1 monochloramine. Similarly,
161
groundwater containing 0.5 mg Cl2·L-1 free chlorine was used to release the L.
162
pneumophila from free-chlorine-treated biofilms. As a control experiment, groundwater
163
free of disinfectant was also used to release L. pneumophila from the monochloramine-
164
treated or free-chlorine-treated biofilms. For the groundwater biofilms without disinfection
7 ACS Paragon Plus Environment
Page 8 of 32
Page 9 of 32
Environmental Science & Technology
165
treatment (untreated biofilms), the pre-adhered L. pneumophila cells were released from
166
biofilms using groundwater, groundwater containing monochloramine, and groundwater
167
containing free chlorine, respectively. For all of the above conditions, the groundwater
168
containing or lacking disinfectant was introduced to the flow chamber for thirty minutes.
169
The detached samples (containing released L. pneumophila and sloughed off biofilm
170
materials) were collected at 1, 2, 3, 4, 5, 10, 20, and 30 min for further analysis of
171
L. pneumophila inactivation and infectivity. The disinfectant in collected samples were
172
immediately quenched using 5% (w/v) sodium thiosulfate. The L. pneumophila release
173
experiment under each condition was repeated three times using biofilm coupons from the
174
same reactor. Each L. pneumophila adhesion-release experiment lasted for two days, and
175
all the L. pneumophila release experiments were conducted within two and a half weeks.
176
Determination of total released L. pneumophila and detached biofilm materials by
177
DNA extraction and qPCR
178
Sample preparation and DNA extraction
179
For determining the number of detached L. pneumophila in the collected samples, DNA of
180
the detached sample collected at each time point was extracted for subsequent qPCR
181
analysis. Specifically, 2 mL of each detached sample was concentrated to 50 L by
182
centrifuging at 17,000 RCF for two minutes and then carefully removing the supernatant.
183
DNA was then extracted from these concentrated samples using the Qiagen DNA
184
extraction kits (DNeasy Blood & Tissue Kit, Hilden, Germany) following manufacturer’s
185
protocol. After extraction, the DNA was stored in the elution solution provided by the
186
Qiagen DNA extraction kit at -20℃ until used.
8 ACS Paragon Plus Environment
Environmental Science & Technology
Page 10 of 32
187
Determination of total released L. pneumophila
188
The total concentration of L. pneumophila (including all of the live cells and disinfected
189
injured cells) in the detached samples were then enumerated by qPCR, following the
190
previous studies.33, 34 The qPCR reactions were performed in the Applied Biosystems
191
7900HT Fast Real-Time PCR system. The mixture used in each qPCR reaction (15 L)
192
contained 2 L extracted DNA, 200 nM reverse primer, 200 nM forward primer, and 7.5
193
L PowerUp™ SYBR® Green Master Mix (Austin, TX). The reverse and forward primers
194
(mip_99F:
195
CCGGATTAACATCTATGCCTTG-3’) were targeted in the macrophage infectivity
196
potentiator (mip) gene of L. pneumophila, which were designed in a previous study.34 The
197
PCR condition used in this study included an initial denaturing step at 95oC for 10 min
198
followed by 40 cycles of 95oC for 10s and 60oC for 1 min. In each qPCR run, 10-fold serial
199
dilutions of DNA standards (5.8×101-5.8×107 copy number·mL-1) were also amplified to
200
create a standard curve. The slope and interception of each standard curve was then used
201
to calculate the copy numbers of the target genes in the extracted DNA samples. The
202
possible effect of qPCR inhibitors in the extracted DNA sample was excluded by running
203
qPCR for a series of diluted extracted DNA samples (Figure S2). The qPCR efficiency was
204
ranged from 0.98 to 1.02. The detection limit was from 101 to 107 copy numbers. Since a
205
loss of DNA may occur during the DNA extraction process, directly using qPCR results
206
(copy numbers) to represent the real concentration of L. pneumophila in the detached
207
samples is not accurate. A linear correlation between the qPCR results and the colony-
208
forming unit (CFU) of L. pneumophila was determined based on the qPCR results for
209
untreated L. pneumophila samples with known CFU (Figure S3). The final concentration
5’-GGATAAGTTGTCTTATAGCATTGGTG-3’
9 ACS Paragon Plus Environment
and
mip_172R:
5’-
Page 11 of 32
Environmental Science & Technology
210
of L. pneumophila in each detached sample was reported as CTotal
211
(CFUqPCR∙mL-1). The details of the method converting between qPCR and L. pneumophila
212
CFU was described previously.33
213
Determination of total released bacteria
214
The number of total detached (released) biofilm bacteria were quantified by qPCR
215
following similar procedures described above. The V3 region of the 16S rRNA gene was
216
amplified by forward primer 341F (5’-CCTACGGGAGGCAGCAG-3’) and reverse
217
primer 518R (5’-ATTACCGCGGCTGCTGG-3’), as described in a previous study.5 The
218
standard curve was generated by serial dilutions (10-fold, 7.7×101-7.7×108 copy
219
number·mL-1) of 16S rRNA standards (540bp) through qPCR. To avoid degradation of the
220
standards, each set of dilutions was thawed and used immediately after loading all the
221
samples. The dilutions of standards were discarded after each thaw. The efficiency of the
222
qPCR was in the range of 0.95 to 1.00. The detection limit was from 101 to 108 copy
223
numbers.
224
Determination of L. pneumophila inactivation
225
When the biofilm-associated L. pneumophila were exposed to the flowing groundwater
226
containing disinfectant, some released L. pneumophila cells would be injured by the
227
disinfectant and become non-culturable. In this study, we defined this process of L.
228
pneumophila losing cultivability during disinfection by using the term “inactivation”. The
229
amount of culturable L. pneumophila in the detached samples was determined by colony
230
counting on the buffered charcoal yeast extract (BCYE) agar plates with 10 g·L-1
231
chloramphenicol. The L. pneumophila strain used in our study was introduced with a
10 ACS Paragon Plus Environment
released L. pneumophila
Environmental Science & Technology
Page 12 of 32
232
chloramphenicol resistance plasmid (pBG307).14, 35 Therefore, only the L. pneumophila
233
cells in the detached samples were likely to grow on the chloramphenicol-contained BCYE
234
plates, while other detached microorganisms from the biofilms were unlikely to grow. The
235
chloramphenicol concentration of 10 g·L-1 was selected because this concentration did
236
not inhibit the growth of L. pneumophila but could still prevent the growth of other bacteria
237
that did not carry the chloramphenicol resistance plasmids (based on the results of the
238
experiments described in SI). After each L. pneumophila release experiment, serial 10-fold
239
dilutions were prepared for each detached sample collected at different time points.
240
Aliquots (100 L) of each dilution were then spread-plated on the duplicated BCYE plates.
241
After incubating these plates at 37 ℃ for five days, the number of characteristic colonies
242
on each plate were counted. The concentration of culturable L. pneumophila in each
243
detached sample (CCulturable L. pneumophila) was then determined by averaging these colony
244
counting results. In this study, the inactivation of L. pneumophila was represented by the
245
ratio of inactivated L. pneumophila over the concentration of total released L. pneumophila,
246
as shown below:
247
Inactivation ratio = 1 −
𝐶𝐶𝑢𝑙𝑡𝑢𝑟𝑎𝑏𝑙𝑒 𝐿.𝑝𝑛𝑒𝑢𝑚𝑜𝑝ℎ𝑖𝑙𝑎 𝐶𝑇𝑜𝑡𝑎𝑙 𝑟𝑒𝑙𝑒𝑎𝑠𝑒𝑑 𝐿.𝑝𝑛𝑒𝑢𝑚𝑜𝑝ℎ𝑖𝑙𝑎
(1)
(CFU·mL-1) is the concentration of the culturable
248
where CCulturable
249
L. pneumophila in each detached sample determined by colony counting; CTotal released L.
250
-1 pneumophila (CFU·mL )
251
and non-culturable L. pneumophila cells) in each detached sample determined by qPCR,
252
as aforementioned. As a previous study has shown that some bacterial cells injured by
253
disinfection may recover after staying in a disinfectant-free condition for some time,36 the
L.
pneumophila
is the concentration of the total L. pneumophila (including culturable
11 ACS Paragon Plus Environment
Page 13 of 32
Environmental Science & Technology
254
possible fluctuation of colony counting results with time was tested for L. pneumophila at
255
0, 1, and 2 days after disinfection (see the SI).
256
Qualitative estimation of L. pneumophila infectivity
257
The infectivity of released L. pneumophila cells was estimated by using Acanthamoeba
258
castellanii (A. castellanii, ATCC 30234), an amoeba host of L. pneumophila commonly
259
found in natural aquatic environments and water supply systems.37 The method of culturing
260
A. castellanii was described previously.38 After each L. pneumophila release experiment,
261
500 L of the detached sample was added into 4.5 mL of A. castellanii liquid culture at a
262
concentration of 8×104 cells·mL-1 and incubated at 30 ℃ for three days. The total amount
263
of L. pneumophila in the mixture was then determined by DNA extraction and qPCR
264
analysis. The qPCR results were also converted to a concentration of L. pneumophila
265
(CFUqPCR·mL-1) using the linear model shown in Figure S3. The infectivity of L.
266
pneumophila was then qualitatively evaluated by the L. pneumophila population (including
267
both viable and non-viable L. pneumophila cells) growth through infecting A. castellanii.
268
Plate counting was not used in this step. The ratio of L. pneumophila concentration after
269
incubating with A. castellanii over the concentration of total released L. pneumophila from
270
biofilms was calculated to represent L. pneumophila infectivity:
271
Infectivity =
𝐶𝑇𝑜𝑡𝑎𝑙 𝐿.𝑝𝑛𝑒𝑢𝑚𝑜𝑝ℎ𝑖𝑙𝑎 𝑎𝑓𝑡𝑒𝑟 𝑖𝑛𝑓𝑒𝑐𝑡𝑖𝑜𝑛 𝐶𝑇𝑜𝑡𝑎𝑙 𝑟𝑒𝑙𝑒𝑎𝑠𝑒𝑑 𝐿.𝑝𝑛𝑒𝑢𝑚𝑜𝑝ℎ𝑖𝑙𝑎
(2)
272
where CTotal L.pneumophila after infection is the final concentration of the L. pneumophila after
273
incubating with A. castellanii.
274
Results and Discussion 12 ACS Paragon Plus Environment
Environmental Science & Technology
275
L. pneumophila and biofilm material release kinetics from biofilms
276
To estimate L. pneumophila release kinetics under continuous flow conditions, the
277
concentrations of total released L. pneumophila were normalized by the initial density of
278
L. pneumophila on biofilm (SI) and plotted as a function of release time (Figure 2). Figure
279
2a shows the normalized concentration of total L. pneumophila (including all live cells and
280
disinfected injured cells) released from monochloramine-treated, free-chlorine-treated, and
281
untreated biofilms during thirty minutes of groundwater flow. The pre-disinfected biofilms
282
(monochloramine- and free-chlorine-treated) used in this study were grown to mimic
283
biofilms that develop in the presence of disinfectant-containing fresh drinking water in a
284
distribution or premise plumbing system. Conversely, the untreated biofilms simulated
285
drinking water biofilms in locations where disinfectant residual is lacking or low, such as
286
in stagnant or corroded-pipe zones.39 From all the studied pre-disinfected and untreated
287
biofilms, the release of L. pneumophila rapidly reduced at the beginning of release process
288
and then leveled off. For example, from the untreated biofilms, the release of
289
L. pneumophila decreased from 0.06±0.02 mm-1 to 0.004±0.003 mm-1 in the first five
290
minutes. However, from the fifth to the thirtieth minute, the released L. pneumophila was
291
not significantly different (0.004±0.003 mm-1 to 0.003±0.003 mm-1, t-test, p=0.54). Also,
292
the normalized concentrations of L. pneumophila released from monochloramine-treated,
293
free-chlorine-treated, and untreated biofilms had comparable values. For example, at the
294
second minute, the total L. pneumophila released from untreated, monochloramine-treated,
295
and free-chlorine-treated biofilms was 0.02±0.009 mm-1, 0.03±0.01 mm-1, and
296
0.01±0.0005 mm-1, respectively (one-way ANOVA, p=0.24). In summary, pre-
297
disinfecting biofilms did not change the L. pneumophila release kinetics.
13 ACS Paragon Plus Environment
Page 14 of 32
Page 15 of 32
Environmental Science & Technology
298
In addition to determining the total released L. pneumophila from biofilms, the total
299
bacterial 16S rRNA gene copies in the detached samples, which represent the released
300
biofilm materials, were also determined (Figure 2b). The change of total released bacterial
301
16S rRNA gene copies as a function of time showed similar trend with the change of total
302
released L. pneumophila. Specifically, the release of biofilm bacteria decreased
303
dramatically at the beginning of release process and then became stable. The total released
304
L. pneumophila and released bacteria as a function of time showed similar trends,
305
suggesting that the release of L. pneumophila always accompanied the detachment of
306
biofilm materials. Previous studies also suggested that sloughing off biofilm materials can
307
release the pathogens into drinking water.12, 40 Moreover, by using the disinfectant-free
308
groundwater to wash the biofilms, biofilm materials released from monochloramine-
309
treated (red triangles) and free-chlorine-treated (green triangles) biofilms were similar.
310
However, higher biofilm materials release was observed for the untreated biofilms (grey
311
circles) compared with the monochloramine- or free-chlorine-treated biofilms (e.g., at 3
312
min, p=0.02, one-way ANOVA). A previous study compared the stiffness of long-term
313
disinfected and untreated simulated drinking water biofilms and reported that the biofilms
314
were stiffer after long-term disinfectant exposure.26 The stiffer biofilms were expected to
315
detach (release) less because of better resistance to flow shear stress.41 Therefore, under
316
the same flow velocity (0.4 ms-1), the biofilm materials released from monochloramine-
317
or free-chlorine-treated biofilms were lower than those from untreated biofilms.
318
Moreover, the release kinetics of L. pneumophila and biofilm materials under different
319
types of disinfectant exposures were compared. Figure 3a shows the normalized
320
concentration of total L. pneumophila released from untreated biofilms by flowing 14 ACS Paragon Plus Environment
Environmental Science & Technology
Page 16 of 32
321
groundwater, groundwater containing monochloramine, and groundwater containing free
322
chlorine as a function of time. Under all the studied disinfectant/disinfectant-free exposure
323
conditions, the fatest L. pneumophila release occurred within the first five minutes of
324
release process. At most of the time points (1, 2, 5, 10, 15, 20, 30 min), the release of L.
325
pneumophila from untreated biofilms under all studied exposure conditions was similar
326
(e.g., at 1 min, p=0.52, one-way ANOVA). However, at the third and the fourth minute,
327
the release of L. pneumophila under monochloramine exposure (e.g., 0.02±0.003 mm-1 at
328
4 min) was higher than those observed under disinfectant-free (e.g., 0.008±0.004 mm-1 at
329
4 min) or free chlorine (e.g., 0.007±0.005 mm-1 at 4 min) exposure conditions. In summary,
330
the exposure to disinfectant did not significantly alter the release kinetics of L.
331
pneumophila from same biofilms.
332
The number of total bacterial 16S rRNA gene copies in the detached samples under
333
different types of disinfectant exposures was also compared (Figure 3b). While the total
334
released bacteria under disinfectant-free and free chlorine exposure conditions was similar,
335
the total released bacteria under monochloramine exposure condition was higher than that
336
under the other two conditions at the third and fourth minute. For example, at the third
337
minute, the total released bacteria under monochloramine exposure was (4.35±0.76)×106
338
copy number·mL-1, which is statistically higher than that under disinfectant-free ((1.55±
339
0.53)×106 copy number·mL-1) and free chlorine exposure ((1.66 ± 0.41)×106 copy
340
number·mL-1)
341
monochloramine exposure led to higher L. pneumophila and biofilm material detachment
342
was presumably due to the higher detachment of biofilm clusters occurring at three to four
343
minutes. Previous studies showed that monochloramine can better penetrate into biofilms
conditions
(one-way
ANOVA,
p=0.03).
15 ACS Paragon Plus Environment
The
observation
that
Page 17 of 32
Environmental Science & Technology
344
and thus may lead to higher cell inactivation/release.42,
345
disinfectant-free and free chlorine exposure conditions, higher bacteria release under
346
monochloramine exposure was observed at three to four minutes.
347
Inactivation of L. pneumophila released from biofilms
348
By using the groundwater flow containing disinfectant to release the biofilm-associated L.
349
pneumophila from biofilms, some L. pneumophila cells were inactivated. The inactivation
350
of L. pneumophila released from biofilms under disinfectant exposure was qualitatively
351
assessed by the ratio of non-culturable L. pneumophila to the total released L. pneumophila
352
(Figure 4). Under all examined conditions, the L. pneumophila inactivation as a function
353
of time revealed two regimes. At the beginning of L. pneumophila release process, the L.
354
pneumophila inactivation ratio increased rapidly. For example, under monochloramine
355
exposure, the ratio of inactivated L. pneumophila released from untreated biofilms (red
356
circles in Figures 4a and 4b) increased from 0.43±0.11 to 0.90±0.05 in the first five minutes.
357
However, with longer disinfectant exposure, the change of inactivation ratio leveled off.
358
The ratio of inactivated L. pneumophila under monochloramine exposure changed from
359
0.90±0.05 to 0.95±0.06 during the fifth to thirtieth minute. The observation of these two
360
regimes could be explained by the L. pneumophila and biofilm materials detachment
361
process. During the first five minutes, superficial L. pneumophila on the biofilm surface
362
was continuously exposed to disinfectant and detached, thus a rapid increase of the
363
inactivation ratio was observed. However, with longer exposures to the flowing
364
groundwater containing monochloramine, the L. pneumophila incorporated into the inner
365
layer biofilms started to be exposed to disinfectant and detached. Those newly exposed L.
16 ACS Paragon Plus Environment
43
Therefore, compared to
Environmental Science & Technology
366
pneumophila cells were not significantly inactivated, thus the inactivation ratio did not
367
dramatically increase from the fifth to the thirtieth minute.
368
By using the flowing groundwater containing same disinfectant to release biofilm-
369
associated L. pneumophila, the inactivation ratios of L. pneumophila released from pre-
370
disinfected and untreated biofilms were compared. As shown in Figure 4a, the L.
371
pneumophila released from monochloramine-treated biofilms showed higher inactivation
372
ratios than that from untreated biofilms. For example, at the first minute, the ratios of
373
inactivated L. pneumophila released from untreated biofilms was 0.43±0.11, which was
374
statistically lower (t-test, p=0.04) than that from monochloramine-treated biofilms
375
(0.83±0.03). Comparison on the inactivation of L. pneumophila released from untreated
376
biofilms and free-chlorine-treated biofilms also showed a similar trend (Figure S4). The
377
lower inactivation ratios for L. pneumophila released from untreated biofilms suggested
378
that L. pneumophila associated with untreated biofilms had better resistance to the
379
disinfectants. As shown in Figure 2b, higher detachment of biofilm materials was observed
380
for the untreated biofilms than the pre-disinfected biofilms. For those L. pneumophila
381
released together with other detached biofilm materials, these biofilm materials could
382
protect L. pneumophila from disinfection by limiting the penetration of disinfectant.44, 45
383
Therefore, higher biofilm materials detachment from untreated biofilms caused the lower
384
ratios of inactivated L. pneumophila released from untreated biofilms. Although
385
disinfectant residual was reported to take limited effect on biofilm removal in distribution
386
or premise plumbing systems,26 exposing biofilms to disinfectants could reduce the risk of
387
L. pneumophila release when L. pneumophila spike occurs.
17 ACS Paragon Plus Environment
Page 18 of 32
Page 19 of 32
Environmental Science & Technology
388
In addition to comparing the L. pneumophila inactivation associated with different
389
types of biofilms, the inactivation ratios of L. pneumophila released under different species
390
of disinfectant exposure were compared. The inactivation ratio of released L. pneumophila
391
from untreated biofilms under monochloramine and free chlorine exposures were not
392
significantly different (Figure 4b, t-test at each time point, all p>0.05). Whereas previous
393
studies reported monochloramine as a stronger biofilm disinfectant, by penetrating
394
biofilms more than free chlorine,42 free chlorine inactivated non-biofilm-associated
395
bacteria more effectively than monochloramine.46 In this study, our qualitative assessment
396
of inactivation and similar effects of either disinfectant may be explained by the overall
397
effect of biofilm-associated and non-biofilm-associated L. pneumophila inactivation.
398
Infectivity of L. pneumophila released from biofilms
399
The infectivity of L. pneumophila was represented by the amplification of L.
400
pneumophila population after infecting A. castellanii. The infectivity of L. pneumophila
401
released from untreated biofilms and pre-disinfected biofilms was compared in Figures 5a
402
and S4. By using monochloramine-contained groundwater to release the L. pneumophila
403
cells from biofilms, the infectivity of L. pneumophila released from untreated biofilms was
404
significantly higher than that released from the monochloramine-treated biofilms (Figure
405
5a). For example, at the end of the L. pneumophila release experiment, the infectivity of L.
406
pneumophila released from untreated biofilms was 6.0±0.6, statistically higher than the
407
infectivity of 0.2±0.1 for L. pneumophila released from the monochloramine-treated
408
biofilms (t-test, p=0.04). Comparison on the infectivity of L. pneumophila released from
409
untreated biofilms and free-chlorine-treated biofilms also showed a similar trend (Figure
410
S5). The higher infectivity of L. pneumophila released from untreated biofilms agreed with 18 ACS Paragon Plus Environment
Environmental Science & Technology
411
the lower inactivation ratio of L. pneumophila released from same biofilms, further
412
suggesting that untreated biofilms can better protect L. pneumophila from disinfection.
413
The infectivity of L. pneumophila released from untreated biofilms under
414
monochloramine, free chlorine, and disinfectant-free exposure conditions was compared
415
in Figure 5b. Under the disinfectant-free exposure condition, the L. pneumophila infectivity
416
at each time point was statistically the same (one-way ANOVA, p=0.98), suggesting that
417
the infectivity of L. pneumophila released from biofilms did not change significantly with
418
time. Specifically, the infectivity was 20±6 at the thirtieth minute, which was constant with
419
the infectivity of 19±5 at the first minute. Compared with the infectivity of released L.
420
pneumophila under disinfectant-free exposure, the L. pneumophila infectivity under
421
disinfectant exposures was significantly lower (t-test, p0.05) and showed a similar trend as a function of time.
424
Specifically, under both monochloramine and free chlorine exposure conditions, the
425
infectivity showed a decrease in the first five minutes, indicating that the overall L.
426
pneumophila population amplification after infecting A. castellanii gradually decreased.
427
The infectivity then became stable from the fifth to the thirtieth minute under
428
monochloramine or free chlorine exposure. In addition, at the thirtieth minute of the
429
monochloramine and free chlorine exposure, (4±2) % and (7±2) % of the total L.
430
pneumophila cells released from untreated biofilms were still culturable, respectively
431
(Figure 4b). Thus, compared with the L. pneumophila released under non-disinfectant
432
condition, the ratio of culturable L. pneumophila cells was twenty five and seventeen times
433
lower under monochloramine and free chlorine exposure, respectively. However,
19 ACS Paragon Plus Environment
Page 20 of 32
Page 21 of 32
Environmental Science & Technology
434
infectivity of L. pneumophila released under monochloramine and free chlorine exposure
435
was only four and three times lower, respectively, than that without disinfectant present
436
(Figure 5b). Therefore, some non-culturable L. pneumophila cells also contributed to the
437
L. pneumophila population growth after infecting A. castellanii. In other words, part of the
438
non-culturable L. pneumophila cells were viable but non-culturable (VBNC) and still had
439
the ability of infecting A. castellanii. The VBNC state was also reported for the planktonic
440
L. pneumophila treated with monochloramine, free chlorine, and heat shock.47-49 The
441
existence of VBNC L. pneumophila released from biofilms under disinfectant exposure
442
suggested that the infectivity of L. pneumophila released from biofilms may not be
443
sufficiently reduced even under disinfectant exposures. When the drinking water
444
disinfectant does not inactivate the biofilm-associated L. pneumophila, some of the L.
445
pneumophila cells would still be healthy, and other cells would turn to a non-viable state
446
and VBNC state (patricianly injured). If amoebae are present in the DWDS system, both
447
healthy and VBNC L. pneumophila cells can infect their host amoebae and replicate inside
448
the amoebae. This L. pneumophila replication process will produce more L. pneumophila
449
with higher virulence, and thus increase L. pneumophila risk and cause more human health
450
concerns.
451
In summary, disinfectant type (free chlorine vs. monochloramine) had no apparent
452
effect on L. pneumophila release nor disinfection. Real drinking water biofilms would be
453
expected to develop with and without disinfectant exposure, with released pathogens
454
becoming inactivated in flowing drinking water containing disinfectant. Our study
455
indicated that compared with the biofilms developed under a disinfectant-free condition,
456
the long-term disinfected biofilms provided less protection for the biofilm-associated
20 ACS Paragon Plus Environment
Environmental Science & Technology
457
pathogens. Although the long-term disinfectant exposure was shown to not effectively
458
remove biofilm biomass,15, 26 the pre-exposing of biofilms to disinfectant could alter the
459
biofilm properties, thus reducing the regrowth and infection risk of pathogens released
460
from biofilms. Secondly, the exposure to free chlorine and monochloramine did not show
461
any obvious difference on inactivating biofilm-associated L. pneumophila. While free
462
chlorine is a stronger and faster-acting oxidizer, it diffuses less into biofilms than
463
monochloramine,42, 43 thus the inactivation efficiency for biofilm-associated pathogens in
464
drinking water distribution systems is a combined effect of disinfectant oxidation strength
465
and diffusion ability. Finally, the results of this study revealed that part of the inactivated
466
L. pneumophila cells could still infect and propagate within amoebae. Therefore, even
467
though the L. pneumophila was inactivated by disinfectant in drinking water, the risk of L.
468
pneumophila reviving in drinking water distribution systems and infecting the human body
469
should be further studied.
470
Supporting Information
471
In support of the methods and results for this study, the SI mainly includes: method
472
description for normalization of L. pneumophila release, the OCT image of biofilms used
473
in this study (Figure S1), qPCR inhibition test (Figure S2), correlation between qPCR and
474
CFU counting (Figure S3), inactivation and infectivity of biofilm-associated L.
475
pneumophila released under free chlorine (Figures S4 and S5), fluorescence microscope
476
image of L. pneumophila adhered on biofilms (Figure S6), groundwater and tap water
477
quality parameters (Tables S1 and S2).
478
Acknowledgements
21 ACS Paragon Plus Environment
Page 22 of 32
Page 23 of 32
Environmental Science & Technology
479
This publication was made possible by research supported by grant R834870 (agreement
480
number RD-83487001) from the U.S. Environmental Protection Agency (EPA). Its
481
contents are solely the responsibility of the grantee and do not necessarily represent the
482
official views of the EPA. Further, the EPA does not endorse the purchase of any
483
commercial products or services mentioned in the publication. We also want to
484
acknowledge Guillermo L. Monroy and Stephen A. Boppart (University of Illinois at Urbana
485
Champaign) for their help in OCT imaging.
486 487
22 ACS Paragon Plus Environment
Environmental Science & Technology
488
References
489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532
1. MDHHS issues 2015 Legionnaires Disease Report for Genesee County; The Michigan Department of Health and Human Services: January 21, 2016. 2. Schwake, D. O.; Garner, E.; Strom, O. R.; Pruden, A.; Edwards, M. A., Legionella DNA Markers in Tap Water Coincident with a Spike in Legionnaires’ Disease in Flint, MI. Environ. Sci. Technol. Lett. 2016, 3, (9), 311-315. 3. Yoder, J.; Roberts, V.; Craun, G. F.; Hill, V.; Hicks, L.; Alexander, N. T.; Radke, V.; Calderon, R. L.; Hlavsa, M. C.; Beach, M. J.; Roy, S. L. Surveillance for Waterborne Disease and Outbreaks Associated with Drinking Water and Water not Intended for Drinking --- United States, 2005--2006; The Center for Surveillance, Epidemiology, and Laboratory Services, Centers for Disease Control and Prevention (CDC), U.S. Department of Health and Human Services: September 12, 2008. 4. Yoder, J.; Roberts, V.; Craun, G. F.; Hill, V.; Hicks, L.; Alexander, N. T.; Radke, V.; Calderon, R. L.; Hlavsa, M. C.; Beach, M. J.; Roy, S. L. Surveillance for Waterborne Disease Outbreaks Associated with Drinking Water --- United States, 2007--2008; The Center for Surveillance, Epidemiology, and Laboratory Services, Centers for Disease Control and Prevention (CDC), U.S. Department of Health and Human Services: September 23, 2011. 5. Person, A.; Benton-Franklin; Spitters, C.; Patrick, G.; Wasserman, C.; Kelen, P. V.; VanEenwyk, J.; Gilboa, S.; Kucik, J.; Sorenson, R.; Ailes, E.; Stahre, M. Surveillance for Waterborne Disease Outbreaks Associated with Drinking Water and Other Nonrecreational Water — United States, 2009–2010; The Center for Surveillance, Epidemiology, and Laboratory Services, Centers for Disease Control and Prevention (CDC), U.S. Department of Health and Human Services: September 6, 2013. 6. Beer, K. D.; Gargano, J. W.; Roberts, V. A.; Hill, V. R.; Garrison, L. E.; Kutty, P. K.; Hilborn, E. D.; Wade, T. J.; Fullerton, K. E.; Yoder, J. S. Surveillance for waterborne disease outbreaks associated with drinking water—United States, 2011–2012; The Center for Surveillance, Epidemiology, and Laboratory Services, Centers for Disease Control and Prevention (CDC), U.S. Department of Health and Human Services: 2015. 7. Cargill, K. L.; Pyle, B. H.; Sauer, R. L.; McFeters, G. A., Effects of culture conditions and biofilm formation on the iodine susceptibility of Legionella pneumophila. Can. J. Microbiol. 1992, 38, (5), 423-429. 8. Giao, M.; Wilks, S.; Azevedo, N.; Vieira, M.; Keevil, C., Incorporation of natural uncultivable Legionella pneumophila into potable water biofilms provides a protective niche against chlorination stress. Biofouling 2009, 25, (4), 345-351. 9. Kim, B.; Anderson, J.; Mueller, S.; Gaines, W.; Kendall, A., Literature review— efficacy of various disinfectants against Legionella in water systems. Water Res. 2002, 36, (18), 4433-4444. 10. Cooper, I.; Hanlon, G., Resistance of Legionella pneumophila serotype 1 biofilms to chlorine-based disinfection. J. Hosp. Infect. 2010, 74, (2), 152-159. 11. Saby, S.; Vidal, A.; Suty, H., Resistance of Legionella to disinfection in hot water distribution systems. Water Sci. Technol. 2005, 52, (8), 15-28. 12. Lau, H.; Ashbolt, N., The role of biofilms and protozoa in Legionella pathogenesis: implications for drinking water. J. Appl. Microbiol. 2009, 107, (2), 368378. 23 ACS Paragon Plus Environment
Page 24 of 32
Page 25 of 32
533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578
Environmental Science & Technology
13. Thomas, J. M.; Thomas, T.; Stuetz, R.; Ashbolt, N. J., Your garden hose: a potential health risk due to Legionella spp. growth facilitated by free-living amoebae. Environ. Sci. Technol. 2014, 48, (17), 10456–10464. 14. Shen, Y.; Monroy, G. L.; Derlon, N.; Janjaroen, D.; Huang, C.; Morgenroth, E.; Boppart, S. A.; Ashbolt, N. J.; Liu, W.-T.; Nguyen, T. H., Role of biofilm roughness and hydrodynamic conditions in Legionella pneumophila adhesion to and detachment from simulated drinking water biofilms. Environ. Sci. Technol. 2015, 49, (7), 4274-4282. 15. Bridier, A.; Briandet, R.; Thomas, V.; Dubois-Brissonnet, F., Resistance of bacterial biofilms to disinfectants: a review. Biofouling 2011, 27, (9), 1017-1032. 16. Sanchez-Vizuete, P.; Orgaz, B.; Aymerich, S.; Le Coq, D.; Briandet, R., Pathogens protection against the action of disinfectants in multispecies biofilms. Front. Microbiol. 2015, 6, 1-12. 17. Schwering, M.; Song, J.; Louie, M.; Turner, R. J.; Ceri, H., Multi-species biofilms defined from drinking water microorganisms provide increased protection against chlorine disinfection. Biofouling 2013, 29, (8), 917-928. 18. Chorianopoulos, N.; Giaouris, E.; Skandamis, P.; Haroutounian, S.; Nychas, G. J., Disinfectant test against monoculture and mixed‐culture biofilms composed of technological, spoilage and pathogenic bacteria: bactericidal effect of essential oil and hydrosol of Satureja thymbra and comparison with standard acid–base sanitizers. J. Appl. Microbiol. 2008, 104, (6), 1586-1596. 19. Lechevallier, M. W.; Cawthon, C. D.; Lee, R. G., Factors promoting survival of bacteria in chlorinated water supplies. Appl. Environ. Microbiol. 1988, 54, (3), 649-654. 20. LeChevallier, M. W.; Cawthon, C. D.; Lee, R. G., Inactivation of biofilm bacteria. Appl. Environ. Microbiol. 1988, 54, (10), 2492-2499. 21. Andreozzi, E.; Barbieri, F.; Ottaviani, M. F.; Giorgi, L.; Bruscolini, F.; Manti, A.; Battistelli, M.; Sabatini, L.; Pianetti, A., Dendrimers and Polyamino-Phenolic Ligands: Activity of New Molecules Against Legionella pneumophila Biofilms. Front. Microbiol. 2016, 7, 1-16. 22. Burmølle, M.; Webb, J. S.; Rao, D.; Hansen, L. H.; Sørensen, S. J.; Kjelleberg, S., Enhanced biofilm formation and increased resistance to antimicrobial agents and bacterial invasion are caused by synergistic interactions in multispecies biofilms. Appl. Environ. Microbiol. 2006, 72, (6), 3916-3923. 23. Hwang, C.; Ling, F.; Andersen, G. L.; LeChevallier, M. W.; Liu, W.-T., Microbial community dynamics of an urban drinking water distribution system subjected to phases of chloramination and chlorination treatments. Appl. Environ. Microbiol. 2012, 78, (22), 7856-7865. 24. Wang, H.; Masters, S.; Edwards, M. A.; Falkinham III, J. O.; Pruden, A., Effect of disinfectant, water age, and pipe materials on bacterial and eukaryotic community structure in drinking water biofilm. Environ. Sci. Technol. 2014, 48, (3), 1426-1435. 25. Bishop, P. L.; Gibbs, J. T.; Cunningham, B. E., Relationship between concentration and hydrodynamic boundary layers over biofilms. Environ. Technol. 1997, 18, (4), 375-385. 26. Shen, Y.; Huang, C.; Monroy, G. L.; Janjaroen, D.; Derlon, N.; Lin, J.; EspinosaMarzal, R.; Morgenroth, E.; Boppart, S. A.; Ashbolt, N. J.; Liu, W.-T.; Nguyen, T. H., Response of simulated drinking water biofilm mechanical and structural properties to long-term disinfectant exposure. Environ. Sci. Technol. 2016, 50, (4), 1779-1787. 24 ACS Paragon Plus Environment
Environmental Science & Technology
579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624
27. Xue, Z.; Lee, W. H.; Coburn, K. M.; Seo, Y., Selective reactivity of monochloramine with extracellular matrix components affects the disinfection of biofilm and detached clusters. Environ. Sci. Technol. 2014, 48, (7), 3832-3839. 28. Xue, Z.; Seo, Y., Impact of chlorine disinfection on redistribution of cell clusters from biofilms. Environ. Sci. Technol. 2013, 47, (3), 1365-1372. 29. Alleron, L.; Merlet, N.; Lacombe, C.; Frere, J., Long-Term Survival of Legionella pneumophila in the Viable But Nonculturable State After Monochloramine Treatment. Current Microbiology 2008, 57, (5), 497-502. 30. Falkinham, J. O.; Pruden, A.; Edwards, M., Opportunistic premise plumbing pathogens: Increasingly important pathogens in drinking water. Pathogens 2015, 4, (2), 373-386. 31. Janjaroen, D.; Ling, F.; Monroy, G.; Derlon, N.; Mogenroth, E.; Boppart, S. A.; Liu, W. T.; Nguyen, T. H., Roles of ionic strength and biofilm roughness on adhesion kinetics of Escherichia coli onto groundwater biofilm grown on PVC surfaces. Water Res. 2013, 47, (7), 2531-42. 32. Virginia Plumbing Code: Chapter 6 Water supply and distribution. https://www2.iccsafe.org/states/Virginia/Plumbing/Plumbing_Frameset.html (05/10/2014), 33. Wang, H.; Edwards, M.; Falkinham, J. O.; Pruden, A., Molecular survey of the occurrence of Legionella spp., Mycobacterium spp., Pseudomonas aeruginosa, and amoeba hosts in two chloraminated drinking water distribution systems. Appl. Environ. Microbiol. 2012, 78, (17), 6285-6294. 34. Ishii, S.; Segawa, T.; Okabe, S., Simultaneous Quantification of Multiple Foodand Waterborne Pathogens by Use of Microfluidic Quantitative PCR. Appl. Environ. Microbiol. 2013, 79, (9), 2891-2898. 35. Chen, D. Q.; Zheng, X. C.; Lu, Y. J., Identification and characterization of novel ColE1-type, high-copy number plasmid mutants in Legionella pneumophila. Plasmid 2006, 56, (3), 167-178. 36. Benjamin, E., 3rd; Reznik, A.; Benjamin, E.; Pramanik, S. K.; Sowers, L.; Williams, A. L., Mathematical models for Enterococcus faecalis recovery after microwave water disinfection. J. Water Health 2009, 7, (4), 699-706. 37. Buse, H. Y.; Lu, J.; Lu, X.; Mou, X.; Ashbolt, N. J., Microbial diversities (16S and 18S rRNA gene pyrosequencing) and environmental pathogens within drinking water biofilms grown on the common premise plumbing materials unplasticized polyvinylchloride and copper. FEMS Microbiol. Ecol. 2014, 88, (2), 280-295. 38. Buse, H. Y.; Lu, J.; Ashbolt, N. J., Exposure to synthetic gray water inhibits amoeba encystation and alters expression of Legionella pneumophila virulence genes. Appl. Environ. Microbiol. 2015, 81, (2), 630-639. 39. Zhang, Z.; Stout, J. E.; Victor, L. Y.; Vidic, R., Effect of pipe corrosion scales on chlorine dioxide consumption in drinking water distribution systems. Water Res. 2008, 42, (1), 129-136. 40. Parsek, M. R.; Singh, P. K., Bacterial biofilms: an emerging link to disease pathogenesis. Annu. Rev. Microbiol. 2003, 57, (1), 677-701. 41. Tierra, G.; Pavissich, J. P.; Nerenberg, R.; Xu, Z.; Alber, M. S., Multicomponent model of deformation and detachment of a biofilm under fluid flow. J. Royal Soc. Interface 2015, 12, (106), 20150045. 25 ACS Paragon Plus Environment
Page 26 of 32
Page 27 of 32
625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646
Environmental Science & Technology
42. Lee, W. H.; Wahman, D. G.; Bishop, P. L.; Pressman, J. G., Free chlorine and monochloramine application to nitrifying biofilm: comparison of biofilm penetration, activity, and viability. Environ. Sci. Technol. 2011, 45, (4), 1412-1419. 43. Türetgen, I., Comparison of the efficacy of free residual chlorine and monochloramine against biofilms in model and full scale cooling towers. Biofouling 2004, 20, (2), 81-85. 44. Chen, X.; Stewart, P. S., Chlorine penetration into artificial biofilm is limited by a reaction-diffusion interaction. Environ. Sci. Technol. 1996, 30, (6), 2078-2083. 45. Miller, H. C.; Wylie, J.; Dejean, G.; Kaksonen, A. H.; Sutton, D.; Braun, K.; Puzon, G. J., Reduced efficiency of chlorine disinfection of Naegleria Fowleri in a drinking water distribution biofilm. Environ. Sci. Technol. 2015, 49, (18), 11125-11131. 46. Au, K.-K., Water treatment and pathogen control: Process efficiency in achieving safe drinking-water. IWA Publishing: 2004. 47. Ducret, A.; Chabalier, M.; Dukan, S., Characterization and resuscitation of ‘nonculturable’cells of Legionella pneumophila. BMC Microbiol. 2014, 14, (1), 1. 48. Alleron, L.; Khemiri, A.; Koubar, M.; Lacombe, C.; Coquet, L.; Cosette, P.; Jouenne, T.; Frere, J., VBNC Legionella pneumophila cells are still able to produce virulence proteins. Water Res. 2013, 47, (17), 6606-6617. 49. Epalle, T.; Girardot, F.; Allegra, S.; Maurice-Blanc, C.; Garraud, O.; Riffard, S., Viable but not culturable forms of Legionella pneumophila generated after heat shock treatment are infectious for macrophage-like and alveolar epithelial cells after resuscitation on Acanthamoeba polyphaga. Microb. Ecol. 2015, 69, (1), 215-224.
647 648 649
26 ACS Paragon Plus Environment
Environmental Science & Technology
650 651 652 653 654 655 656
Figure 1 Biofilm preparation and L. pneumophila release experiment process. Biofilms were developed from groundwater for 1 year, and then distributed to three reactors for subsequent six months of disinfectant exposures. Next, the L. pneumophila cells were allowed to adhere and incorporate into biofilms. Finally, these biofilm-associated L. pneumophila cells were released using the groundwater flow containing or lacking disinfectant.
657
27 ACS Paragon Plus Environment
Page 28 of 32
Page 29 of 32
Environmental Science & Technology
658 659 660 661 662 663 664
Figure 2 Total a) L. pneumophila and b) bacteria released from untreated biofilms, monochloramine-treated biofilms, and free-chlorine-treated biofilms, respectively. The total released L. pneumophila in the y axis of a) was calculated by normalizing the concentration of released L. pneumophila (#/mL) by the initially adhered L. pneumophila on biofilms (#/mm2). The total released biofilm bacteria in the y axis of b) was represented by 16S rRNA qPCR results (copy number·mL-1).
665
28 ACS Paragon Plus Environment
Environmental Science & Technology
666 667 668 669 670 671 672 673 674
Figure 3 Total a) L. pneumophila and b) bacteria released from untreated biofilms as a function of time. The groundwater, groundwater containing monochloramine, and groundwater containing free chlorine were continuously flowing through biofilms and detached L. pneumophila and other bacteria from biofilms, respectively. The total released L. pneumophila in the y axis of a) was calculated by normalizing the concentration of released L. pneumophila (#/mL) by the initially adhered L. pneumophila on biofilms (#/mm2). The total released bacteria in the y axis of b) was represented by 16S rRNA qPCR results (copy number·mL-1).
675 676
29 ACS Paragon Plus Environment
Page 30 of 32
Page 31 of 32
Environmental Science & Technology
677 678 679 680 681 682
Figure 4 a) Inactivation ratio of L. pneumophila released from untreated and monochloramine-treated biofilms under monochloramine exposure. b) Inactivation ratio of L. pneumophila released from untreated biofilms under monochloramine and free chlorine exposures. The inactivation ratio was defined by the ratio of non-cultivable L. pneumophila to total released L. pneumophila.
683
30 ACS Paragon Plus Environment
Environmental Science & Technology
684 685 686 687 688 689
Figure 5 a) Infectivity of L. pneumophila released from untreated biofilms and monochloramine-treated biofilms under monochloramine exposure. b) Infectivity of L. pneumophila released from untreated biofilms by monochloramine and free chlorine. The infectivity was defined by the ratio of L. pneumophila population after infecting amoeba to L. pneumophila population before infecting amoebae.