Performance Evaluation of Two 25 kW Residential Wood Pellet Boiler

Oct 16, 2017 - (19-24) The overall tank efficiency (φ) is defined as (10)Simultaneously, tank discharge efficiency (φdis) is defined as (11)where Ec...
2 downloads 13 Views 2MB Size
Subscriber access provided by University of Florida | Smathers Libraries

Article

Performance Evaluation of Two 25 kW Residential Wood Pellet Boiler Heating Systems Kui Wang, Mauro Masiol, Devraj Thimmaiah, Yuanyuan Zhang, and Philip K. Hopke Energy Fuels, Just Accepted Manuscript • DOI: 10.1021/acs.energyfuels.7b01868 • Publication Date (Web): 16 Oct 2017 Downloaded from http://pubs.acs.org on October 17, 2017

Just Accepted “Just Accepted” manuscripts have been peer-reviewed and accepted for publication. They are posted online prior to technical editing, formatting for publication and author proofing. The American Chemical Society provides “Just Accepted” as a free service to the research community to expedite the dissemination of scientific material as soon as possible after acceptance. “Just Accepted” manuscripts appear in full in PDF format accompanied by an HTML abstract. “Just Accepted” manuscripts have been fully peer reviewed, but should not be considered the official version of record. They are accessible to all readers and citable by the Digital Object Identifier (DOI®). “Just Accepted” is an optional service offered to authors. Therefore, the “Just Accepted” Web site may not include all articles that will be published in the journal. After a manuscript is technically edited and formatted, it will be removed from the “Just Accepted” Web site and published as an ASAP article. Note that technical editing may introduce minor changes to the manuscript text and/or graphics which could affect content, and all legal disclaimers and ethical guidelines that apply to the journal pertain. ACS cannot be held responsible for errors or consequences arising from the use of information contained in these “Just Accepted” manuscripts.

Energy & Fuels is published by the American Chemical Society. 1155 Sixteenth Street N.W., Washington, DC 20036 Published by American Chemical Society. Copyright © American Chemical Society. However, no copyright claim is made to original U.S. Government works, or works produced by employees of any Commonwealth realm Crown government in the course of their duties.

Page 1 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

1

Performance Evaluation of Two 25 kW Residential

2

Wood Pellet Boiler Heating Systems

3

Kui Wang,1.2 Mauro Masiol,1 Devraj Thimmaiah, 1 Yuanyuan Zhang, 1 Philip K. Hopke1,2*

4

1. Center for Air Resources Engineering and Science

5

2. Department of Chemical and Biomolecular Engineering

6

Clarkson University

7

Potsdam, NY 13699 USA

8

ABSTRACT

9

A significant increase in the use of wood pellets for residential space heating has occurred over

10

the past decade. The performance of two modern residential wood pellet boilers (designated PB

11

and WPB) were evaluated including boiler thermal efficiency, thermal energy storage (TES) tank

12

discharge efficiency, and system efficiency. A correlation applicable to both systems between the

13

boiler thermal efficiency (ηth, in %) and the boiler output load (χ, in %) was found in the form of

14

ηth = 52.69 ln χ – 137.7 with R2 = 0.79 (for 25 < χ < 75). This equation provides an easy,

15

accurate estimation of the boiler thermal efficiency in field operations. The boiler thermal

16

efficiency decreased with time and this decline was determined using a Mann-Kendall trend

17

analysis with Sen’s slope. This decrease was primarily the result of fouling in the heat

18

exchanger and thus, this analysis identifies the need for manual cleaning of the heat exchanger

19

tubes to restore maximal system performance. The evaluation of the TES tank performance

20

found that the TES tank discharge efficiency was correlated with a dimensionless function of

21

tank inlet Reynolds number (Red) and temperature differences in the tank and inlet and outlet

22

pipes. Overall system efficiency showed a seasonal average of 62.8%, 62.0%, and 75.8% for

23

three heating seasons of the PB system. These results provide a comprehensive performance

24

evaluation of these wood pellet boiler heating systems in the field over an extended period of

25

operation.

26 27

Keywords: wood pellet boiler; thermal efficiency; Sen’s slope; TES tank performance

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

28 29 30

Page 2 of 23

Nomenclature Btotal: energy to the tank from boiler, kJ

∆Td:

cp,w: water specific heat, kJ/(kg·K) Echa: energy to building during tank charge, kJ Edis:

energy to building discharge, kJ

during

tank

HHV: pellet fuel higher heating value, MJ/kg

TES tank inlet/outlet temperature difference, °C

∆Td,ave: average TES tank inlet/outlet temperature difference during discharge, °C ∆Ts: TES tank top and bottom temperature difference, °C

Mw: pellet fuel moisture content (w.b.)

∆Ts,ave: average TES tank top and bottom temperature difference during discharge, °C

N: boiler nominal load, kW

ε: boiler stoker feed fraction

Q: boiler loop flow rate, m3/h

ηth: boiler thermal efficiency, %

Q*: building loop flow rate, m3/h

ηsys: system efficiency, %

Red: inlet pipe Reynolds number

κ100: boiler stoker feed rate at 100%, kg/h

tc: time of a complete burn cycle, h

ξ: TES tank flow factor

td: boiler off time or tank discharge time, h

ρw: water density, kg/m3

T1: boiler output water temperature, °C

φ: TES tank overall efficiency (cycle basis), %

T1*: TES tank output water temperature, °C T2: boiler return water temperature, °C T2*: TES tank return water temperature, °C

φdis: TES tank discharge efficiency, % χ: boiler output load, %

∆t: boiler flow meter recording interval, s

ACS Paragon Plus Environment

Page 3 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

31 32

Energy & Fuels

1. Introduction Because of the increasing interest in the use of renewable energy, biomass has been

33

increasingly utilized over the past decade. According to IEA, bioenergy provides 10% of world

34

primary energy supply currently1 and biofuels can provide up to 27% of world transportation fuel

35

by 2050.2 Generally, biomass refers to any material that is derived directly or indirectly from

36

plants.3 Biomass, especially wood and wood pellets, is becoming more widely used as an

37

alternative energy source for domestic space heating due to its relatively high energy density and

38

uniform quality compared to cordwood or chips.4 In the European Union, wood pellet use is

39

growing rapidly due to government policies to meet renewable energy targets.3,4,5

40

Wood pellets offer both economic and climate benefits. Wood can be harvested sustainably

41

and provide a substantial local energy supply as well as offering extra employment to collect and

42

process the wood. Chau et al.6 provided a detailed techno-economic evaluation of a small scale

43

wood pellet heating system. Wood pellet boiler technology has also improved over the past

44

decades particularly driven by European interest in utilizing a local, renewable fuel. Modern

45

wood pellet boilers have high efficiency and low pollutant emissions. Fiedler7 reviewed the state

46

of the art of small-scale pellet combustion units for domestic use and the individual EU country

47

regulations where more stringent regulations are likely to appear in the future. Öhman et al.8

48

studied the slagging tendencies in residential wood pellet boilers related to ash sintering

49

temperatures. They found that wood pellets have a low sintering tendency (sintering

50

temperatures higher than 1100 °C) mainly due to the low alkali and Si content in the fuel.9 Hence,

51

modern wood pellet boilers utilize moving grates or sliding grate ash removal systems.7 Better

52

combustion chamber and flow geometry can be designed and optimized by applying

53

computational fluid dynamics (CFD) simulations.10,11 In addition, studies have shown that when

54

firing with non-woody biomass pellets, better boiler control such as fuel feeding, air intake, and

55

ash management is required.12

56

A key index for assessing the performance of wood pellet boiler is its thermal efficiency.

57

There are many factors affecting the thermal efficiency of wood pellet boilers. Chandrasekaran et

58

al. characterized the efficiency of two wood pellet boilers13 and wood stoves burning multiple

59

types of pellets14. Efficiencies ranged from 70% to 91% for different boilers running with wood

60

pellets and from 75% to 85% when burning with non-woody pellets. Verma et al.15,16 found that

61

the performance of a domestic pellet boiler is a function of the boiler operational loads. Carlon

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

62

et al.17 reported a non-linear relationship between thermal efficiency and a modified load factor.

63

Several factors lead to the efficiency-load relationships. The most important factor is the excess

64

air ratio that is usually higher under low load conditions. In addition, low load conditions cannot

65

generate sufficient turbulence for complete combustion, which leads to low combustion

66

efficiency and temperatures.16 Heat transfer is also reduced during low load conditions. Thus, it

67

is better for the boiler to operate at high or full load condition so that maximum thermal

68

efficiency can be achieved.

69

Depending on the building load and the ambient temperature, the building may not require all

70

of the heat produced by the boiler when it operates at full load. The use of thermal energy

71

storage (TES) enables the wood pellet boiler to operate for longer periods at higher loads and,

72

consequently, reduces the number of boiler ignitions and avoids short-cycling during warmer

73

weather. TES in the form of large insulated water tanks was initially utilized in solar water

74

heating systems because the stratification inside the tank can help to extract more useful heat

75

from the tank.18 Many experimental and numerical studies have been performed to study the

76

performance of TES tank in terms of temperature stratification, efficiency, and operational

77

behavior.19-25

78

The present work systematically evaluated the performance of two modern wood pellet

79

heating systems in terms of: boiler thermal efficiency at various loads, TES tank discharge

80

efficiency and overall system efficiency based on long-term monitoring from 2015 to 2017.

81

Currently, there are no such systematic evaluations of in-use wood pellet heating systems for

82

such an extended period.

83 84

2. Material and Methods

85

2.1 The Two Systems

86

In this project, two nominally identical 25 kW wood pellet boilers were installed in two

87

homes in northern New York State with different configurations (as shown in Figure 1). In each

88

boiler, wood pellets are fed by a stoker screw auger into the combustion chamber from the top of

89

the burner pot. A hot air gun ignites the pellets. Primary air enters the combustion chamber from

90

the bottom of the burner pot. Hot combustion gas passes through a 3-stage fire tube heat

91

exchanger to transfer heat into jacket water and exhausts through the chimney. The induced draft

92

fan at the end of the flue gas pathway controls the primary air flow through a Lambda sensor (O2

ACS Paragon Plus Environment

Page 4 of 23

Page 5 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

93

control) (calibrated with an external combustion analyzer) and a negative pressure sensor (draft

94

control). Within each fire tube, there is a twisted turbulator to improve heat transfer as well as to

95

clean the inside surfaces of the fire tubes by moving the turbulators up and down. The residual

96

ash is removed from the bottom ash collector. The boiler is controlled by software that records

97

its operational data.

98 99

2.2 Pellet Fuel Characterization

100

The pellets used in this study are PFI (Pellet Fuels Institute26) certified premium pellets.

101

Samples were collected during bulk delivery to the pellet bins. The pellets were characterized

102

for heating value, moisture, composition, and ash content. Detailed analytical methods and

103

results are listed in Table 1. The pellets have a mean calorific content of 19.12 MJ/kg (or 8221

104

Btu/lb) higher heating value (HHV), 3.88% moisture, 0.58% ash, and 46.64% carbon.

105 106

Table 1. Summary of analytical methods and results Parameter

Method

Result

HHV

ASTM E 711-87 (2004)

19.12 MJ/kg (a.r.)

Moisture

ASTM E 871-82 (2006)

3.88% (w.b.)

Ash

ASTM D 1102-84 (2007)

0.58% (d.b.)

Carbon

ASTM E 777-87 (2004)

46.64% (d.b.)

Hydrogen

ASTM E 777-87 (2004)

6.4% (d.b.)

Nitrogen

ASTM E 778-87 (1996)

0.14% (d.b.)

Oxygen

By difference

46.23% (d.b.)

Chlorine

ASTME 776-87 (2009)

0.00388% (d.b.)

Sulfur

ASTM E 775-87 (2004)

0.00689% (d.b.)

107 108

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

109 110

2.3 Experimental Methods Figure 1 shows the two system configurations as operated during the 2016-17 heating season.

111

These systems had each undergone modification over time and detailed histories of each system

112

are presented in the Supporting Information. The PB (Parishville boiler) system was installed in

113

a modified shipping container near a family house in Parishville NY, USA (44.63 N, 74.83 W,

114

271 m a.s.l.) replacing their existing outdoor wood boiler (OWB). Hot water from the boiler was

115

stored in two identical TES tanks (A.O. Smith Co., volume of each = 0.45 m3) and then delivered

116

to the house for space heating through an underground circulation system. The tanks provided

117

36.0 liter per kW (2.8 gallons per kBtu/h) storage, above manufacturer recommendations of 25.7

118

liter per kW (2 gallons per kBtu/h). Return water from the building flowed to the bottom of the

119

tanks. This house has a total heating area of 406.5 m2 with an estimated peak load of 27 kW

120

(92000 Btu/h). The tanks store hot water from the boiler at temperature ranging from 55°C

121

(131°F) to 75°C (167°F) that is used for a radiant floor heating system with return water

122

temperatures ranging from 35°C (95°F) to 45°C (113°F), depending on outdoor temperature and

123

the thermostat settings.

124

The other nominal 25 kW boiler was installed in the basement of a family house located in

125

West Potsdam, NY, USA (44.69 N, 75.09 W, 122 m a.s.l.). An existing oil boiler was integrated

126

into the system as an auxiliary boiler. This system is denoted as WPB (West Potsdam boiler)

127

system. A single 210-gallon TES tank (0.79 m3) was installed in the system. In this system, the

128

TES tank was installed in a 2-pipe configuration such that both the boiler and the heat demand

129

are on the same side of the tank. In addition, WPB system had a 0.1 m3 domestic hot water

130

(DHW) tank that provided domestic hot water. The additional oil boiler and the DHW tank

131

made both the system control and the boiler behavior different from PB system.

132

For both systems, flow and temperature were monitored in two loops: boiler to tank loop and

133

tank to building loop to calculate heat output from the boiler and the TES tank, respectively. A

134

certified ultrasonic flow meter (EF-10 series, Spire Metering Technology) and two temperature

135

probes were installed in each loop. The boiler was controlled by two temperature sensors in the

136

TES tank (bottom ON and top OFF).

137

To determine the energy input rate, the boiler stoker feed auger was calibrated at several feed

138

rates. The pellets were collected in a weighed bucket and after a fixed time, the bucket was

139

weighed. From these results, the maximum feed rates (κ100) were determined to be 12.98 kg/h

ACS Paragon Plus Environment

Page 6 of 23

Page 7 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

140

and 12.17 kg/h for PB and WPB, respectively. The constant speed augers are modulated by

141

operating them only a part of the time (feed fraction, ε). The actual feed fractions are recorded at

142

1 second intervals by each boiler. Using the fuel characterization data, the heat input into the

143

boiler can be calculated as the product of the mass flow rate and the calorific content of the

144

pellets. It was found that the augers were quite reproducible over time such that multiple

145

calibrations produced essentially identical relationships between time of auger operation and

146

mass flow rates of fuel delivered into the boiler.

147

The operation of these boiler-thermal storage systems was characterized in terms of “system

148

cycles” that began with the start-up of the boiler, steady-state combustion, boiler shut down, and

149

finally depletion of heat from the thermal storage system to the building until the boiler restarted

150

because the control temperature at the top of the thermal storage tank had been reduced to the

151

setpoint value. Within these system cycles, there are “boiler cycles.” A complete boiler cycle

152

includes three phases: start-up, steady state combustion, and burnout/shutdown.

153

For PB system, measurements were made over three heating seasons denoted as PB-1, PB-2,

154

and PB-3. PB-1 included data from February 1, 2015 to April 11, 2015 representing 493 cycles;

155

PB-2 included data from December 1, 2015 to April 1, 2016 with a total of 392 cycles; and PB-3

156

included data from January 5, 2017 to April 5, 2017 with a total of 372 cycles. During PB-1 and

157

PB-2, the thermal storage tanks were continuously connected to the circulation loop that

158

conducted heat to the building (See Supplemental Figure SI-3). Water was continuously

159

circulated through this loop to avoid freezing in the underground line. Before PB-3, a 3-way

160

valve was installed (Figure 1, top) such that the circulation loop was separated from the thermal

161

storage tanks when there was no demand for heat from the house. Local weather data obtained

162

from Weather Underground27 were used in this study.

163

For WPB system, major changes had been made over the prior heating seasons to address

164

operational problems that had been identified (see supplemental information). Thus, only WPB-

165

3 data were used for the performance analysis. WPB-3 ran from December 28, 2016 to April 12,

166

2017 and included a total of 644 cycles.

167 168 169 170

2.4 Efficiency Calculations Because of the slower start-up and shut down associated with solid fuel combustion, the boiler thermal efficiency was calculated based on each boiler cycle. Overall efficiency was

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Page 8 of 23

171

calculated based on system cycles. For each boiler cycle, the boiler thermal efficiency (ηth) was

172

calculated as the ratio of heat output to heat input over each cycle time (tc)  =

∑ , ( –  ) ∙ Δ  ∑(HHV ∙  ∙  )

× 100%

(1)

173

where ∆t is ultrasonic flowmeter data sampling interval (10 s). The boiler stoker feed fraction ε

174

was recorded every 1 s.

175

System efficiency is defined based on system cycles. It is the total energy delivered into the

176

building during a system cycle divided by the total energy input into the boiler for each boiler

177

cycle, as #$# =

178

∑&' ∗  , ( ∗ –  ∗ ) ∙ Δ  ∑(HHV ∙  ∙  )

× 100%

where td is the time when boiler is off until next boiler cycle.

ACS Paragon Plus Environment

(2)

Page 9 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

179

180 181

Figure 1. Schematic of the PB (top) and WPB (bottom) systems with data acquisition devices (S-

182

1: flue gas O2 control signal, S-2: boiler pump control signal; S-3: Boiler ON signal; S-4: Boiler

183

OFF signal)

184

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

185

3. Results and Discussion

186

3.1 Boiler Thermal Efficiency

187

Page 10 of 23

During a boiler cycle, the instantaneous efficiency of the boiler changes. Low efficiency

188

occurs during start-up due to inefficient combustion during the ignition and stabilization stages

189

when there are also high CO and particle emissions.28 As the combustion stabilizes, the boiler

190

thermal efficiency reaches its highest value during its steady state operation. Low efficiencies

191

again occur as the boiler shuts down and the residual fuel burns out. Thus, boiler thermal

192

efficiency over each cycle is an appropriate metric for boiler performance.

193

Figure 2 shows the regression between boiler thermal efficiency and boiler output load

194

percentage for both boiler systems. For the PB system, due to boiler software updates and

195

frequent setting change of TES tank ON/OFF temperatures during PB-2 and PB-3, a relatively

196

low r2 = 0.68 was determined. However, when these parameters remained fixed in PB-1, the r2

197

rose to 0.86. For the WPB system, the operation of DHW significantly affected the boiler cycling

198

characteristics, as explained in the supporting information. Because the DHW tank represented a

199

low thermal mass, very little energy was dissipated into the domestic hot water. When the boiler

200

was ON because of demand from the thermal storage tank and the DHW was also demanding

201

heat, the DHW tank acts as an independent TES tank. However, the low heat dissipation in the

202

DHW tank resulted in very high boiler return water temperatures that approached the safety limit

203

set temperature of the boiler. Therefore, the boiler reduced its output quickly sometimes causing

204

boiler short cycling. The problem was reduced during WPB-3 by defining wider temperature set-

205

points for DHW tank but controls alone could not eliminate the problem.

206 207

A general regression equation based on four datasets for the two systems was determined by merging the data and fitting an equation as follows: ηth = 52.69 ln χ – 137.7

(for 25< χ i), n is the number of total data points, and sgn(xj - xi ) is the

272

sign function defined as

273

+1, sgn234 − 3 6 = : 0, −1,

(7)

Mann30 and Kendall31 have shown that when n ≥ 18, S is approximately a normal distribution

274 275

34 − 3 > 0 34 − 3 = 0 34 − 3 < 0

with expectation of 0 and variance as >

 (-)

?(? − 1)(2? + 5) − ∑B 8  ( − 1)(2 + 5) = 18

ACS Paragon Plus Environment

(8)

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Page 14 of 23

276

where m is the number of tied groups and ti denotes the number of ties of extent i. A tied group is

277

defined as a set of samples with the same value. The standard normal test (or Z-test) statistic ZS

278

is computed as

279

-−1 , if - > 0 I GJ>  (-) DE = 0, if - = 0 H -+1 G , if - < 0 FJ>  (-)

280

usually used to estimate the slope of the trend (also called Sen’s slope analysis). Figure 4 shows

281

the analysis results for PB and WPB systems.

282

(9)

ZS > 0 means increasing trends while ZS < 0 means decreasing trends. A Theil-Sen’s line is

A decreasing trend in boiler thermal efficiency can be observed in Figure 4(a) when there

283

was no manual cleaning performed. High boiler thermal efficiency of around 85% was initially

284

observed after the boiler installation. An average rate of -0.022 % per boiler cycle was

285

determined for PB-1. Therefore, if the boiler must be cleaned manually when the thermal

286

efficiency has dropped by 10%, PB has to be cleaned after 455 boiler cycles. Given an average

287

of 7 boiler cycles per day, the boiler needs to be cleaned after ~65 days of continuous operation.

288

Figure 4(b) shows a relatively constant trend of boiler thermal efficiency for PB-2, which

289

suggests that the boiler can only maintain around 70% thermal efficiency based on its internal

290

cleaning mechanism. After two manual cleanings were performed during PB-3, the boiler

291

thermal efficiency significantly improved compared to PB-2. For WPB-3, an average boiler

292

thermal efficiency rate of -0.038% per boiler cycle was determined, which means WPB must be

293

manually cleaned after 263 boiler cycles or ~38 days of continuous operation given the same

294

evaluating criterion as PB. WPB-3 had the higher rate of decline in the boiler thermal efficiency.

295

One factor for this boiler could be the high moisture content in the basement. This old basement

296

has little ventilation and standing water was often observed on the basement floor on rainy days.

297

When the boiler was manually cleaned at the beginning of WPB-3, the cleaning turbulators had

298

to be replaced due to substantial fouling and corrosion. In a high moisture environment, it is

299

much easier to have condensation in the boiler, which facilitates boiler fouling and corrosion

300

ACS Paragon Plus Environment

Page 15 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

(a). PB-1

(b). PB-2

(c). PB-3

(d). WPB-3

301 302

Figure 4. Sen’s slope of boiler thermal efficiency for PB and WPB systems (c.i. – confidence

303

interval)

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

304 305

process. Thus, operation of a dehumidifier in these circumstances may improve the boiler performance.

306 307

3.3 Thermal Storage Tank Performance

308

The TES tank top and bottom temperatures are measured by the ON and OFF temperature

309

sensors inserted into sensor wells in the tank as shown in Figure 1. The TES tank top and bottom

310

temperature difference (∆Ts) can be used to assess tank stratification since a well stratified tank

311

has a larger ∆Ts. Figure 5 shows tank behavior during a complete system cycle in PB-1.

312 313

Figure 5. TES tank temperature distribution during one complete boiler burn cycle in PB-3

314 315

The vertical dashed lines divide the system cycle into charge and discharge periods. During

316

the TES tank charging period, the boiler heats the tank to the set temperature. Then the boiler

317

shuts down, and the tank discharges heat to the building. The amount of energy discharged is

318

determined by the stratification inside the tank since a well stratified tank has higher exergy than

ACS Paragon Plus Environment

Page 16 of 23

Page 17 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

319

a completely mixed tank.32 The TES tank can continuously supply energy to the building without

320

interruption depending on the building demand.

321 322

A well stratified tank can discharge more energy than a completely mixed tank, as shown in earlier studies.19-24 The overall tank efficiency (φ) is defined as φ = (Echa + Edis)/Btotal × 100%

323

(10)

Simultaneously, tank discharge efficiency (φdis) is defined as φdis = Edis/(Btotal – Echa) × 100%

(11)

324

where Echa and Edis are energy delivered to the building during charge and discharge periods,

325

respectively; Btotal is the total energy delivered to the tank during a complete boiler cycle.

326

Tank discharge efficiency, φdis, is a good indicator of the stratification inside the tank when

327

the boiler is off. Studies have shown that two major factors affect the stratification: tank

328

geometry (inlet/outlet positions,20 tank aspect ratio,19 baffle plates,23 etc.) and operational

329

conditions (temperature difference,33 flow rates,33 operation modes,21,22 etc.). The present

330

evaluation focuses on these operational conditions because the tanks had a fixed geometry during

331

the entire monitoring period and the TES tank was operated with continuous flow on the building

332

side for PB system during the first two heating seasons.

333

Figure 6(a) shows TES tank top and bottom average temperature difference (∆Ts,ave) over

334

each discharge period as a function of corresponding discharge time td (or boiler off time) for

335

PB-1 data. The correlation equation is shown below (R2 = 0.83) ∆Ts,ave = 66.75(td)-1 – 150.0(td)-2 + 119.3(td)-3 – 5.965

ACS Paragon Plus Environment

(12)

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Page 18 of 23

336 337

Figure 6. (a): TES tank top and bottom average temperature difference as a function of discharge

338

time for PB-1; (b): Tank discharge efficiency correlated with dimensionless flow factor for PB-1

339 340

Longer discharge times indicate less heat demand from the building (i.e. warmer weather)

341

that result in smaller temperature differences in the tank since the TES tank supply and return

342

water temperatures will be closer in temperature. Then, no clear thermocline may develop in the

343

tank.34 Consequently, when the building is demanding heat, a larger ∆Ts,ave will occur due to the

344

larger temperature difference between the TES tank supply and return water temperatures. Figure

345

6(a) shows that stratification of a TES tank in the heating system is highly dependent on the

346

building heat load. This result suggests that maintaining stratification inside the tank at low

347

building heat loads can be attained by decreasing the flow rate to create a larger return water

348

temperature difference from the tank top temperature. Figure 6(b) shows TES tank discharge efficiency φdis is correlated with a dimensionless

349 350

number ξ by the following equation (r2 = 0.73) ln φdis = 8.3 – 175.3ξ

(13)

351

where φdis is in %, and ξ is expressed in pipe Reynolds number (Red) and temperature differences

352

as ξ = (∆Ts,ave /∆Td,ave)0.35(Red)-0.41

(14)

353

where ∆Ts,ave is the average TES tank top and bottom temperature difference during discharge

354

period and ∆Td,ave is the average TES tank supply and return temperature difference during the

355

same discharge period. Figure 6(b) indicates that an increase in Red and decrease in ∆Ts,ave

ACS Paragon Plus Environment

Page 19 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

356

/∆Td,ave will lead to an exponential increase in tank discharge efficiency. For a specific TES tank,

357

increasing the Red means an increased flow rate, which corresponds with previous studies that

358

the TES tank discharge efficiency (or extraction efficiency) increases with increasing flow

359

rate.19,24,33 Thus, inlet flow diffusers and baffles23,24,35 are used to minimize flow mixing and

360

maintain a high level of stratification. The ratio of ∆Ts,ave /∆Td,ave is an indicator of the amount of

361

heat delivered to the building. The maximum value of ∆Ts,ave /∆Td,ave is 1 when there is no heat

362

delivered to the building or the return water temperature is equal to the temperature at the bottom

363

of TES tank. Small ratios suggest large TES tank supply and return temperature differences,

364

which further indicate large amounts of heat consumed by the building.

365

For PB-2 and PB-3, correlations between ∆Ts,ave and td, φdis and ξ have much lower R2 values

366

compared to PB-1 data as shown in Figure 6. This result is caused by the constant TES tank

367

ON/OFF setting maintained over the whole heating season for PB-1, but a variety of TES tank

368

ON/OFF settings were explored during PB-2 and PB-3 that in turn reduced the correlation. For

369

WPB-3, the TES tank stratification (∆Ts) was constantly disturbed by the DHW tank operation.

370

Therefore, the correlation was worse than for PB-2 and PB-3. In addition, the 2-pipe

371

configuration prohibits the determination of the exact amount of energy delivered into the TES

372

tank since part of the energy produced while the boiler is on can be directed to the DHW tank.

373

Therefore, no correlation for TES tank discharge efficiency can be established. An additional

374

flowmeter on the DHW tank loop would have been required to permit this calculation.

375

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

376 377

3.4 System Efficiency System efficiency evaluates the efficiency of the whole system based on the heat delivered to

378

the building and the heat input into the boiler. The average seasonal system efficiency values

379

were 62.8%, 62.0%, and 75.8% for PB-1, PB-2, and PB-3, respectively. Low system efficiencies

380

during PB-1 and PB-2 was mostly due to the low thermal efficiencies and low TES tank

381

discharge efficiencies when there was no 3-way valve installed to prevent the constant

382

circulation of the building circulator as shown in Figure 1 (as discussed in supplemental

383

information). After effective boiler cleaning and system modification, the system efficiency in

384

PB-3 significantly increased. System efficiencies for WPB could not calculated because the

385

current measurement system did not permit the determination of the amounts of heat input

386

transferred into both the TES tank and the building based on the 2-pipe configuration system.

387 388

4. Conclusions and Suggestions

389

4.1 Conclusions

390

The objective of this study was to evaluate the performance of two 25 kW residential wood

391

pellet boilers in terms of boiler thermal efficiency, thermal energy storage (TES) tank discharge

392

efficiency, and system efficiency based on long term field site monitoring results. A general

393

correlation between boiler thermal efficiency (ηth, in %) and boiler output load percentage (χ,

394

in %) was determined to be ηth = 52.69 ln χ – 137.7 with r2 = 0.79 (for 25 < χ < 75) for both

395

systems. Evaluation of thermal efficiency bins showed that most of time, the PB boiler was

396

operating above 70% efficiency with seasonal average thermal efficiencies of 73.6%, 70.8%, and

397

79.0% for PB-1, PB-2, and PB-3, respectively. However, the WPB boiler was operating below

398

70% thermal efficiency most of the time caused by the DHW induced load modulation and

399

severe boiler fouling. A Sen’s slope analysis on the boiler thermal efficiency can determine the

400

boiler thermal efficiency decreasing rate and provide information on when additional cleaning is

401

needed. The results showed that the PB boiler had a thermal efficiency drop of 0.022% per boiler

402

cycle and could maintain around 70% boiler thermal efficiency without manual cleaning. The

403

WPB boiler had a thermal efficiency drop of 0.038% per boiler cycle and must be cleaned every

404

38 days (given an average of 7 boiler cycles per day). TES tank performance showed a

405

correlation of the tank discharge efficiency with a dimensionless number that is a function of

406

inlet pipe Reynolds number and temperature differences in both the tank and pipe inlet/out. The

ACS Paragon Plus Environment

Page 20 of 23

Page 21 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

407

system efficiency evaluation revealed that effective boiler cleaning and system modification can

408

enhance overall system performance. Overall system efficiency showed seasonal averages of

409

62.8%, 62.0%, and 75.8% for PB-1, PB-2, and PB-3, respectively. Future work will be focused

410

on continuing monitoring and performing dynamic process simulation of the system for further

411

optimization. The boiler emissions will be discussed separately in a future manuscript.

412 413 414

4.2 Suggestions for Improvement (1). High moisture content in the combustion air can accelerate wood pellet boiler fouling, as

415

shown in WPB installation. Therefore, it is important to ensure a low moisture content

416

environment for the wood pellet boiler such as adding a dehumidifier to high moisture content

417

environment.

418

(2). The 2-pipe configuration does not necessarily perform better than the traditional 4-pipe

419

configuration. It is important to recognize the effect of the thermal mass of the different heat

420

demanding units connected to the system such that the boiler short-cycling and load modulation

421

shown in WPB system can be avoided. An alternative 3-pipe configuration might solve the

422

problem.

423

(3). Frequent manual cleaning of the heat exchanger is essential to maintaining high overall

424

system performance for these wood pellet heating systems. The decline in the thermal efficiency

425

can serve as an indicator of the need for additional cleaning.

426 427

Acknowledgements

428

This work was supported by the New York State Energy Research and Development Authority

429

(NYSERDA) under agreements #32977 and 63007. We want to express our thanks to the

430

homeowners of the boiler systems for their willingness to work with us to assess the

431

effectiveness of this technology. John Siegenthaler of Appropriate Designs and Khaled Yousef

432

of Pyramid Energy Engineering Services, PLLC are acknowledged for their advice on system

433

design and modifications. We also want to acknowledge the cooperation of the boiler

434

manufacturer in helping to address issues as they were identified.

435 436 437

ACS Paragon Plus Environment

Energy & Fuels

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

438

Page 22 of 23

References (1) International Energy Agency (IEA), available at https://www.iea.org/topics/renewables/subtopics/bioenergy/. (2) International Energy Agency (IEA), available at https://www.iea.org/newsroomandevents/pressreleases/2011/april/biofuels-can-provide-up-to27of-world-transportation-fuel-by-2050-iea-report-.html. (3) Demirbas, A. Biomass resource facilities and biomass conversion processing for fuels and chemicals. Energy Convers Manage 2001, 42, 1357-78. (4) Goh, C.S.; Junginger, M.; Cocchi M.; Marchal, D.; Thrän, D.; Hennig, C.; et al. Wood pellet market and trade: a global perspective. Biofuels Bioprod Biorefin 2013, 7, 24-42. (5) Parikka, M. Global biomass fuel resources. Biomass Bioenergy 2004, 27, 613-20. (6) Chau, J.; Sowlati, T.; Sokhansanj, S.; Preto, F.; Melin, S.; Bi, X. Techno-economic analysis of wood biomass boilers for the greenhouse industry. Appl Energy 2009, 86, 364-71. (7) Fiedler, F. The state of the art of small-scale pellet-based heating systems and relevant regulations in Sweden, Austria and Germany. Renew Sustain Energy Rev 2004, 8, 201-21. (8) Öhman, M.; Boman, C.; Hedman, H.; Nordin, A.; Boström, D. Slagging tendencies of wood pellet ash during combustion in residential pellet burners. Biomass Bioenergy 2004, 27, 585-96. (9) Vega-Nieva, D.J.; Torres, L.; Tabares, J.; Morán J. Measuring and Predicting the Slagging of Woody and Herbaceous Mediterranean Biomass Fuels on a Domestic Pellet Boiler. Energy Fuels 2016, 30, 1085-95. (10) Porteiro, J.; Collazo, J.; Patiño, D.; Granada, E.; Gonzalez, J.C.M.; Míguez, J.L. Numerical modeling of a biomass pellet domestic boiler. Energy Fuels 2009, 23, 1067-75. (11) Chaney, J.; Liu, H.; Li, J. An overview of CFD modelling of small-scale fixed-bed biomass pellet boilers with preliminary results from a simplified approach. Energy Convers Manage 2012, 63, 149-56. (12) Carvalho, L.; Wopienka, E.; Pointner, C.; Lundgren, J.; Verma, V.K.; Haslinger, W.; et al. Performance of a pellet boiler fired with agricultural fuels. Appl Energy 2013, 104, 286-96. (13) Chandrasekaran, S.R.; Laing, J.R.; Holsen, T.M.; Raja, S.; Hopke, P.K. Emission characterization and efficiency measurements of high-efficiency wood boilers. Energy Fuels 2011, 25, 5015-21. (14) Chandrasekaran, S.R.; Hopke, P.K.; Newtown, M.; Hurlbut, A. Residential-scale biomass boiler emissions and efficiency characterization for several fuels. Energy Fuels 2013, 27, 4840-9. (15) Verma, V.K.; Bram, S.; Gauthier, G.; Ruyck, J.D. Performance of a domestic pellet boiler as a function of operational loads: Part-2. Biomass Bioenergy 2011, 35, 272-9. (16) Verma, V.K.; Bram, S.; Delattin, F.; Ruyck, J.D. Real life performance of domestic pellet boiler technologies as a function of operational loads: A case study of Belgium. Appl Energy 2013, 101, 357-62. (17) Carlon, E.; Schwarz, M.; Golicza, L.; Verma, V.K.; Prada, A.; Baratieri, M.; et al. Efficiency and operational behaviour of small-scale pellet boilers installed in residential buildings. Appl Energy 2015, 155, 854-65. (18) Hollands, K.G.T.; Lightstone, M.F. A review of low-flow, stratified-tank solar water heating systems. Sol Energy 1989, 43, 97-105. (19) Lavan, Z.; Thompson, J. Experimental study of thermally stratified hot water storage tanks. Sol Energy 1977, 19, 519-24.

ACS Paragon Plus Environment

Page 23 of 23

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

Energy & Fuels

(20) Shah, L.J.; Furbo, S. Entrance effects in solar storage tanks. Sol Energy 2003, 75, 337-48. (21) Fernandez-Seara, J.; Uhia, F.J.; Sieres, J. Experimental analysis of a domestic electric hot water storage tank. Part I: Static mode of operation. Appl Therm Eng 2007, 27,129-36. (22) Fernandez-Seara, J.; Uhia, F.J.; Sieres, J. Experimental analysis of a domestic electric hot water storage tank. Part II: dynamic mode of operation. Appl Therm Eng 2007, 27,137-44. (23) Levers, S.; Lin, W. Numerical simulation of three-dimensional flow dynamics in a hot water storage tank. Appl Energy 2009, 86, 2604-14. (24) Han, Y.M.; Wang, R.Z.; Dai, Y.J. Thermal stratification within the water tank. Renew Sustain Energy Rev 2009, 13, 1014-26. (25) Rosen, M.A.; Dincer, I. Exergy methods for assessing and comparing thermal storage systems. Int J Energy Res 2003, 27, 415-30. (26) Pellet Fuels Institute, available at http://www.pelletheat.org/joining-the-standards-program. (27) Weather History & Data Archive, available at https://www.wunderground.com. (28) Win, K.; Persson, T. Emissions from residential wood pellet boilers and stove characterized into start-up, steady operation, and stop emissions. Energy Fuels 2014, 28, 2496-505. (29) Sippula, O.; Hytönen, K.; Tissari, J.; Raunemaa, T; Jokiniemi, J. Effect of wood fuel on the emissions from a top-feed pellet stove. Energy Fuels 2007, 21, 1151-60. (30) Mann, H.B. Nonparametric tests against trend. Econometrica, 1945, 13, 245–259. (31) Kendall, M.G. Rank Correlation Methods. 1975, Griffin, London, UK. (32) Rosen, M. A. The exergy of stratified thermal energy storages. Sol Energy, 2001, 71, 173185. (33) Hariharan, K.; Murthy, M.V.K. Temperature stratification in hot-water storage tanks. Energy 1991, 16, 977-82. (34) Abdoly, M.A.; Rapp, D. Theoretical and experimental studies of stratified thermocline storage of hot water. Energy Convers Manage 1982, 22, 275-85. (35) Altuntop, N.; Arslan, M.; Ozceyhan, V.; Kanoglu, M. Effect of obstacles on thermal stratification in hot water storage tanks. Appl Therm Eng 2005, 25, 2285-98.

ACS Paragon Plus Environment