Reverse Osmosis Shifts Chloramine Speciation Causing Re

Jul 3, 2017 - However, recent research has demonstrated that laundry effluent may be a dominant source of ozone- and chloramine-reactive NDMA precurso...
0 downloads 14 Views 643KB Size
Subscriber access provided by UNIVERSITY OF CONNECTICUT

Article

Reverse Osmosis Shifts Chloramine Speciation Causing ReFormation of NDMA during Potable Reuse of Wastewater Daniel L. McCurry, Ken Ishida, Gregg Oelker, and William A. Mitch Environ. Sci. Technol., Just Accepted Manuscript • DOI: 10.1021/acs.est.7b01641 • Publication Date (Web): 03 Jul 2017 Downloaded from http://pubs.acs.org on July 6, 2017

Just Accepted “Just Accepted” manuscripts have been peer-reviewed and accepted for publication. They are posted online prior to technical editing, formatting for publication and author proofing. The American Chemical Society provides “Just Accepted” as a free service to the research community to expedite the dissemination of scientific material as soon as possible after acceptance. “Just Accepted” manuscripts appear in full in PDF format accompanied by an HTML abstract. “Just Accepted” manuscripts have been fully peer reviewed, but should not be considered the official version of record. They are accessible to all readers and citable by the Digital Object Identifier (DOI®). “Just Accepted” is an optional service offered to authors. Therefore, the “Just Accepted” Web site may not include all articles that will be published in the journal. After a manuscript is technically edited and formatted, it will be removed from the “Just Accepted” Web site and published as an ASAP article. Note that technical editing may introduce minor changes to the manuscript text and/or graphics which could affect content, and all legal disclaimers and ethical guidelines that apply to the journal pertain. ACS cannot be held responsible for errors or consequences arising from the use of information contained in these “Just Accepted” manuscripts.

Environmental Science & Technology is published by the American Chemical Society. 1155 Sixteenth Street N.W., Washington, DC 20036 Published by American Chemical Society. Copyright © American Chemical Society. However, no copyright claim is made to original U.S. Government works, or works produced by employees of any Commonwealth realm Crown government in the course of their duties.

Page 1 of 27

Environmental Science & Technology

1

Reverse Osmosis Shifts Chloramine Speciation Causing Re-Formation of NDMA during Potable Reuse of Wastewater

2 3 4 5 6 7 8 9 10 11 12 13 14 15

Daniel L. McCurry1,2, Kenneth P. Ishida3, Gregg L. Oelker4, William A. Mitch1,5* 1

2

19 20 21 22 23 24 25 26

Present Address: Department of Civil and Environmental Engineering, University of Southern California, Los Angeles, CA 90089 3

4

16 17 18

Department of Civil and Environmental Engineering, Stanford University, Stanford, CA 94305

5

Orange County Water District, Fountain Valley, CA 92708

Suez, Edward C. Little Reclamation Facility, El Segundo, CA 90245

National Science Foundation Engineering Research Center for Re-Inventing the Nation’s Urban Water Infrastructure (ReNUWIt), 473 Via Ortega, Stanford, California 94305, United States

*Corresponding author phone: (650) 725-9298; fax: (650) 723-7058; e-mail: [email protected]

ACS Paragon Plus Environment

Environmental Science & Technology

27 28

ABSTRACT UV-based advanced oxidation processes (AOPs) effectively degrade N-

29

nitrosodimethylamine (NDMA) passing through reverse osmosis (RO) units within advanced

30

treatment trains for the potable reuse of municipal wastewater. However, certain utilities have

31

observed the re-formation of NDMA after the AOP from reactions between residual chloramines

32

and NDMA precursors in the AOP product water. Using kinetic modeling and bench-scale RO

33

experiments, we demonstrate that the low pH in the RO permeate (~5.5) coupled with the

34

effective rejection of NH4+ promotes conversion of the residual monochloramine (NH2Cl) in the

35

permeate to dichloramine (NHCl2) via the reaction: 2 NH2Cl + H+ ↔ NHCl2 + NH4+.

36

Dichloramine is the chloramine species known to react with NDMA precursors to form NDMA.

37

After UV/AOP, utilities generally use lime or other techniques to increase the pH of the finished

38

water to prevent distribution system corrosion. Modeling indicated that, while the increase in pH

39

halts dichloramine formation, it converts amine-based NDMA precursors to their more reactive,

40

neutral forms. With modeling, and experiments at both bench-scale and field-scale, we

41

demonstrate that reducing the time interval between RO treatment and final pH adjustment can

42

significantly reduce NDMA re-formation by minimizing the amount of dichloramine formed

43

prior to reaching the final target pH.

44 45 46 47

INTRODUCTION

48

purified municipal wastewater as a reliable source of potable water. Advanced treatment trains

49

for potable reuse frequently employ Full Advanced Treatment (FAT), a combination of

50

microfiltration (MF), reverse osmosis (RO) and advanced oxidation processes (AOPs; typically

51

the UV/hydrogen peroxide AOP).1 A recent water reuse risk assessment identified disinfection

Droughts in the United States Southwest and California have increased interest in

ACS Paragon Plus Environment

Page 2 of 27

Page 3 of 27

Environmental Science & Technology

52

byproducts (DBPs) as important chemicals of potential human health concern, particularly N-

53

nitrosodimethylamine (NDMA).2 NDMA is an extremely potent carcinogen; 0.7 ng/L in drinking

54

water is associated with a 10-6 excess lifetime cancer risk, orders of magnitude lower than for

55

many regulated DBPs.3 NDMA is the subject of a WHO standard (100 ng/L)4, California

56

implemented a statewide drinking water notification level of 10 ng/L,5 and the compound is

57

under consideration for federal regulation.6

58

NDMA has long been associated with wastewater reuse. NDMA occurs in domestic

59

sewage,7 but is also associated with industrial discharges.8 NDMA also forms during ozonation

60

or chloramination of amine precursors9,10 and NDMA precursors are particularly associated with

61

wastewater.9-11 Attempting to identify the source of NDMA precursors in wastewater is an active

62

field of research. Certain pharmaceuticals that can occur in sewage form NDMA at high yield

63

(e.g., methadone14 and ranitidine15,16). However, recent research has demonstrated that laundry

64

effluent may be a dominant source of ozone- and chloramine-reactive NDMA precursors in

65

domestic sewage; although specific precursors were not identified, they were not associated with

66

detergents.7 NDMA forms by reaction of these precursors with the chloramines or ozone17,18

67

applied upstream of MF in FAT treatment trains to control biofouling. This NDMA is only

68

partially removed by RO.19 Indeed, the detection of NDMA in the RO permeate of Water

69

Factory 21, one of the nation’s first potable reuse facilities, led to the suspension of operations in

70

2000 pending the installation of a UV system to photolyze NDMA post-RO.20,21

71

Hydrogen peroxide addition converts UV systems to AOPs to degrade other

72

contaminants that may pass through RO membranes (e.g., 1,4-dioxane), but direct photolysis of

73

NDMA remains a key criterion for selecting UV fluence.1 UV-based AOPs typically reduce

74

NDMA concentrations to non-detectable levels (