Chapter 13

Systematic Approach for Safely Designing a Chemical Surety Materiel Laboratory

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

George E. Collins, Jr. Chemical Research Development and Engineering Center, Attn: SMCCR-SFC, Aberdeen Proving Ground, MD 21010-5423

This article shows, through example, how established system safety concepts can be used to develop safety criteria for the design of a chemical surety materiel laboratory. This systematic approach, when applied as described in this article, results in a laboratory dedicated to achieve mission objectives in an environment relatively free of inherent hazards for the least number of dollars.

F a c i l i t y System Safety (FSS), which i s the a p p l i c a t i o n of system safety concepts t o the f a c i l i t y a c q u i s i t i o n process, has recently gained acceptance throughout the Department of Defense and most recently w i t h i n the Department of Army with the conception of SAFEARMY 1990. The Army's goal i s to: f u l l y integrate the t o t a l system safety, human f a c t o r s , and health hazard assessments i n t o continuous comprehensive evaluation of selected systems and f a c i l i t i e s . The Chemical Research Development and Engineering Center (CRDEC) has mandated appropriate l e v e l s of system safety throughout the l i f e c y c l e of f a c i l i t y development f o r many reasons. These include: 1. Optimum safety and health are required to prevent personal i n j u r y to chemical surety agents. F a c i l i t y System Safety i s one avenue used to achieve optimum safety and health i n operations that deal with these agents. 2. FSS i s a proactive approach which w i l l reduce inconsistencies during the f a c i l i t y a c q u i s i t i o n process. This r e s u l t s i n a more mission responsive f a c i l i t y that i s less expensive. The intended purpose of t h i s a r t i c l e i s to demonstrate, through s p e c i f i c examples, how FSS can be applied to the design/construction/operation of a chemical surety materiel laboratory. The laboratory under study i s a 32 m i l l i o n d o l l a r M i l i t a r y Construction, Army (MCA) project designed to replace aging f a c i l i t i e s which are c u r r e n t l y u t i l i z e d to perform d a i l y Chemical Surety M a t e r i e l (CSM) operations. For the purpose of t h i s a r t i c l e , CSM i s defined as a This chapter not subject to U.S. copyright Published 1987 American Chemical Society

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

13.

COLLINS

Designing a Chemical Surety Materiel Laboratory

213

chemical compound used i n m i l i t a r y operations to k i l l , s e r i o u s l y i n j u r e or incapacitate a person through chemical properties. This a r t i c l e demonstrates the methods used i n i d e n t i f y i n g , analyzing and u l t i m a t e l y eliminating or reducing the e f f e c t of a hazard on the f a c i l i t y , equipment and personnel.

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

F a c i l i t y System Safety Overview. The process of applying system safety to the f a c i l i t y a c q u i s i t i o n process can be divided i n t o the following tasks: 1. 2. 3. 4.

Risk Categorization Preliminary Hazard L i s t Preliminary Hazard Analysis Design Considerations

The remainder of t h i s a r t i c l e w i l l involve a d e s c r i p t i o n of each of these tasks followed by an example of how the task was applied to the design of t h i s CSM laboratory. Risk Categorization. The f i r s t step i n t h i s process i s to c l e a r l y define the r i s k associated with the operation of t h i s laboratory. This step includes a b r i e f d e s c r i p t i o n of the operation followed by a r i s k assessment and a recommendation on the l e v e l of system safety required. Laboratory Description. The laboratory under consideration w i l l conduct d i v e r s i f i e d chemical surety materiel laboratory operations. These materials are a n t i c h o l i n e r g i c agents and are extremely l e t h a l i n small concentrations. The recommended permissible airborne exposure concentration f o r some of these agents i s 0.0001 mg/m3 (2 χ 10-5 ppm). Two personnel are required, as a minimum, to per­ form t h i s operation. Assessment. An analysis of the hazards present i n t h i s laboratory show the most s i g n i f i c a n t hazard to be the release of vapor CSM from engineering controls and into the workplace. The s i g n i f i c a n c e of t h i s hazard mandates further e f f o r t s i n system safety i n the form of a Preliminary Hazard L i s t (PHL) and a Preliminary Hazard Analysis (PHA). The user must i n t h i s instance take an a c t i v e r o l e i n the design review process. Preliminary Hazard L i s t . Once the r i s k categorization i s completed, the next step i s to develop a PHL. The PHL i s a user generated l i s t i n g of hazards which must be c o n t r o l l e d . The user must, at t h i s stage, assign a r i s k assessment code to each hazard and e s t a b l i s h any further requirements f o r analyses (the methodology used i n the development of r i s k assessment codes i n t h i s a r t i c l e i s shown as Figure 1). As a minimum the user should use the following sources of information f o r PHL development: 1. 2. 3. 4. 5.

M a t e r i a l Safety Data Sheets F e a s i b i l i t y Studies Project Development Brochures Standing Operating Procedures Operator Interviews

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

TOXIC CHEMICAL AND EXPLOSIVES FACILITIES

214

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

Hazard Severity (1) Category I - Catastrophic: May cause death or loss of a f a c i l i t y . (2) Category I I - C r i t i c a l : May cause severe i n j u r y , severe occupa­ t i o n a l i l l n e s s , or major property damage. (3) Category I I I - Marginal: May cause minor i n j u r y , minor occupa­ t i o n a l i l l n e s s , or minor property damage. (4) Category IV - N e g l i g i b l e : Probably would not a f f e c t personnel safety or health, but i s nevertheless i n v i o l a t i o n of s p e c i f i c standards. Mishap P r o b a b i l i t y (1) (2) (3) (4)

Subcategory Subcategory Subcateogry Subcategory

A Β C D

-

L i k e l y to occur immediately. Probably w i l l occur i n time. May occur i n time. U n l i k e l y to occur.

Risk Assessment Code

Hazard Severity

I II III IV

Mishap Probability A Β C 1 1 2 1 2 3 2 3 4 3 4 5

D 3 4 5 5

Figure 1. Risk Assessment

Preliminary Hazard L i s t Description. The incorporation of t h i s information into a PHL entry i s shown as Table I . This entry describes; the nature of the hazardous event (column 1), why or how the hazard may r e s u l t i n a mishap (column 2), the e f f e c t s on operating personnel, equipment, and the f a c i l i t y (column 3), the r i s k assessment code assigned t o the uncontrolled hazard (column 4) and any comments the o r i g i n a t o r may have (column 5). Preliminary Hazard Analysis. The next step i n the process i s the development of a PHA. This analysis i s the core of the FSS program and as such i s v i t a l i n eliminating or reducing the inherent hazards associated with t h i s laboratory operation. The PHA i s used to further analyze the data i d e n t i f i e d i n the PHL. This enhances the hazard control data base and provides s p e c i f i c recommended correc­ t i v e action f o r the r e s o l u t i o n of hazardous conditions. A combina­ t i o n of the informational sources used i n the PHL development and any a d d i t i o n a l design information should be used i n PHA development.

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

13.

COLLINS

Table I .

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

215

Designing a Chemical Surety Materiel Laboratory P r e l i m i n a r y Hazard

List

COLUMN 1

COLUMN 2

COLUMN 3

COLUMN 4

COLUMN 5

HAZARDOUS EVENTS

CAUSAL FACTORS

EFFECTS

RISK ASS. CODE

COMMENTS

Release of vapor CSM from lab hood and into workplace or atmosphere.

1. Power failure

1. Loss or lab hood capture. Release of CSM into workplace. Personnel injury or death, System/f acuity damage minimal.

I A1

None

2. Mech. exhaust fan failure

2. Same as //l above. I Β 1

None

3. Poor lab hood capture design)

3. Turbulence may IΒ 1 result in small re­ lease of CSM into workplace. Personnel injury or death could result. System/facility damage minimal.

None

4. Operator error

4. Judgement errors could result in an inadvertent release of CSM into the work­ place. Personnel injury or death could result. System/facil­ ity damage minimal.

None

5. Filters do not remove CSM from exhaust

5. Personnel injury II C 3 to people surrounding the facility. System/ facility damage minimal Adverse publicity.

Scenario less likely and severe due to dilu­ tion factor.

6. Exhaust ductwork not properly sealed

6. Small concentra­ tions CSM in the workplace possible in the event the exhaust system were to go positive. Personnel injury or death possi­ ble. System/facility damage minimal.

Scenario less likely due to addi­ tional require­ ment for system to go posi­ tive.

IΒ1

I C2

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

216

TOXIC CHEMICAL AND EXPLOSIVES FACILITIES Table I I .

Preliminary Hazard Analysis

COLUMN 6

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

RECOMMENDED ACTIONS

COLUMN 7

COLUMN 8

CONTROLLED RISK ASS. CODE

STANDARDS

Causal Factor / / l ; IV D 5 a.) Emergency generator system shall be installed to automatically initiate in the event of a power failure, system phasing shall be accomplished in a manner which will not permit the occurrence of a hazardous condition.

DOD 6055.9-STD AMCR 385-102 CRDECR 385-1

b. ) Laboratory hoods must be equipped with a mechanism to warn operators of emergency power status and hood function. c. ) Standing Opeating Procedures should contain provisions for the curtailment of operations, immediate masking and evacuation from areas that experience power failures. Causal Factor //2; a. ) Two alternatives are available to prevent a hazardous condition from occurring in the event of a mechanical failure. These include: (1) Redundant exhaust fan units, (2) Procedural controls which require curtailment of operations, donning of protective masks and immediate evacuation during ventilation loss.

IV D 5

DOD 6055.9-STD AMCR 385-102 CRDECR 385-1 LOCAL SOPs

IV D 5

AMCR 385-102 AEHA Technical Guide y/30 CRDECR 385-1

b. ) Laboratory hoods shall be equipped with a means to warn operators of improper ventilation system functioning. Causal Factor //3: a.) Laboratory hoods must be located away from: - Main traffic aisles and doorways - Adjacent walls and operable windows - Cross drafts exceeding 30 lfpm - Heating Units - Exits.

b.) Laboratory hoods must perform as follows: - Average inward face velocity of 100 lfpm +/- 10% with the velocity at any point not deviating from the average face velocity by more than 20%.

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

13.

COLLINS

Table I I .

Designing a Chemical Surety Materiel Laboratory

Continued COLUMN 6

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

RECOMMENDED ACTIONS

COLUMN 7

COLUMN 8

CONTROLLED RISK ASS. CODE

STANDARDS

IV D 5

CRDECR 385-1

Causal Factor //3 (Continued): c.) Operators must be trained in proper operation within a laboratory hood. Causal Factor /M: a. ) Operating personnel must be properly trained. b. ) Operating personnel must wear appropriate protective clothing. c. ) Operating personnel must work under a properly approved SOP. Causal Factor //5: a.) Exhaust filtration system shall meet CSL SOP 70-18.

IV D 5

CSL SOP 70-18 CRDECR 385-1

Causal Factor //6: a.) Ductwork shall be sealed to preclude leakage.

IV D 5

DOD 6055.9-STD CRDECR 385-1

b. ) A l l joints shall be seamless welded. c. ) Ductwork shall be capable of withstanding 16 inches water column vacuum and 25 inches water column positive pressure.

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

217

218

TOXIC CHEMICAL AND EXPLOSIVES FACILITIES Table I I I . COLUMN 9

COLUMN 11

COLUMN 1 2

DESIGN CERTIFICATION

CONSTRUCTION CERTIFICATION

Drawing //:099 Specification Section //09991

Mr. Smith

Mr. Jones

b. ) Laboratory hoods equipped with warning devices to notify operator of power loss

Drawing //:061 Specification Section #08001

Mr. Smith

Mr. Jones

c. ) Installation notified of finding

Disposition Form sent 6 Jan 86 to safety office

ACTION TAKEN

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

Hazard Tracking Log

CAUSAL FACTOR //It a. ) Emergency generator installed and properly phased

CAUSAL FACTOR //2; a. ) Installation safety office determines need to go with procedural controls. SOPs will be developed accordingly. b. ) Laboratories equipped with warning devices to notify operators of ventilation system failure

COLUMN 1 0

TRANSFER

Disposition Form 10 Jan 86

Drawing //:061 Specification Section #08001

CAUSAL FACTOR //3: a.) Lab hoods meet the Drawing #:045 following: Away from: - Main traffic aisles - Doorways and windows - Adjacent walls - Cross drafts > 30 lfpm - Heating units - Exits

Mr. Smith

Mr. Jones

Mr. Smith

Mr. Jones

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

13.

COLLINS

219

Designing a Chemical Surety Materiel Laboratory

Table I I I . Continued COLUMN 9

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

ACTION TAKEN

COLUMN 10

TRANSFER

CAUSAL FACTOR //3; (Continued) Drawing //:046 b.) Lab hoods perform as Specification follows: Section //07010 - Average face velocity 100 lfpm +/- 10%. No single reading deviating from average by 20% - Smoke testing did not result in a release of visible smoke c.) Installation notifed of requirement for proper training of operators

COLUMN 11

COLUMN 12

DESIGN CERTIFICATION

CONSTRUCTION CERTIFICATION

Mr. Smith

Mr. Jones

Disposition Form dated 25 Mar 86

CAUSAL FACTOR //4: Installation responsibility

Installation notified 25 Mar 86

CAUSAL FACTOR //5; Exhaust system complies with CSL SOP 70-18

Specification Section //01001

Mr. Smith

Mr. Jones

CAUSAL FACTOR //6: Ductwork properly sealed and tested

Specification Section //02000

Mr. Smith

Mr. Jones

Disposition Form dated 25 Mar 86

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

TOXIC CHEMICAL AND EXPLOSIVES FACILITIES

220

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

Preliminary Hazard Analysis Description. The incorporation of t h i s information into a PHA entry i s shown as Table I I . This entry describes; the proposed actions needed to eliminate or c o n t r o l the hazard (column 6), the r i s k assessment code assigned a f t e r controls (column 7), and the i d e n t i f i c a t i o n of applicable codes and standards (column 8). Hazard Tracking Log. In a d d i t i o n to the above a n a l y s i s , a hazard tracking l o g (HTL) should be maintained. This log i s to ensure a l l open loops are closed and ensures the appropriate l e v e l of management i s i d e n t i f i e d as being involved i n the acceptance of r i s k . This log should be i n i t i a t e d during the design phase and maintained throughout construction. As t h i s f a c i l i t y i s not at the design stage at the time of p u b l i c a t i o n , a simulated HTL was used and i s shown at Table I I I . This entry describes: the s p e c i f i c action taken to eliminate, c o n t r o l or accept the hazard (column 9), the reference of the blueprint/drawing numbers or other documents that address the action taken (column 10), name of i n d i v i d u a l closing out the action on design (column 11), and the name of the i n d i v i d u a l c l o s i n g out the action during construction (column 12). The information contained i n t h i s l o g i s proposed because the laboratory i s i n the design stage of development. Laboratory Design Considerations. As a r e s u l t of t h i s e f f o r t , d e t a i l e d safety design considerations can be developed to preclude the release of l e t h a l concentrations of vapor CSM into the workplace. This w i l l minimize the p o t e n t i a l f o r death or serious i n j u r y to our research s c i e n t i s t s . A summary of these requirements i s shown i n Appendix A. Conclusions. The e f f o r t put f o r t h i n FSS f o r t h i s laboratory has many b e n e f i t s . Most noteworthy are: 1. Safest possible laboratory 2. More mission responsive f a c i l i t y 3. Less expensive f a c i l i t y This a r t i c l e i s a step i n the d i r e c t i o n we must a l l head toward and that i s t o t a l system safety f o r f a c i l i t i e s to reduce inherent hazards associated with t h e i r operation. Literature Cited 1. 2. 3. 4.

Chemical Systems Laboratory Standing Operating Procedure (CSL SOP) 70-18, 10 Nov 82, Exhaust Ventilating Systems. Department of Defense (DOD) 6055.9 - STD, July 1984, Ammunition and Explosives Safety Standards. Army Materiel Command Regulation (AMCR) 385-102, 6 May 1982, Safety Regulations for Chemical Agents GB and VX. Chemical Research Development and Engineering Center Regulation (CRDECR) 385-1, 15 Aug 1986, Chemical and Occupational Safety and Health Program.

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

COLLINS

Designing a Chemical Surety Materiel Laboratory

221

APPENDIX A Laboratory Design Considerations for Protection Against Vapor Chemical Surety M a t e r i e l Exposure

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

E l e c t r i c a l Design Considerations (Causal Factor / / l ) : 1. Emergency generator systems w i l l be i n s t a l l e d to service the f o l l o w i n g : -

Exhaust v e n t i l a t i o n fans Make-up a i r handling u n i t s C r i t i c a l operating equipment Emergency l i g h t i n g A l l emergency alarm systems

2.

Diesel-powered generators w i l l be used. The emergency generator w i l l be sized to handle 100% of the connected emergency load.

3.

Start-up of the exhaust v e n t i l a t i o n system and c r i t i c a l equipment must be sequenced to prevent a hazardous condition. In a d d i t i o n , the s t a r t i n g of the supply a i r handling u n i t and the exhaust fan services each room s h a l l i n i t i a t e simultaneously to avoid placing the room under p o s i t i v e pressure. Automatic t r a n s f e r switching w i l l be used.

Warning Systems (Causal Factor 111 & 2): 1. F a c i l i t y w i l l be equipped with a master c o n t r o l panel and alarms which permits f u n c t i o n a l v e r i f i c a t i o n of the exhaust blowers, f i l t e r s , make-up a i r supply systems, f i r e c o n t r o l systems and waste treatment processes. 2.

Laboratory hoods w i l l be equipped with audible and v i s u a l alarms which w i l l be designed to i n i t i a t e when the average inward face v e l o c i t y f a l l s below 90 l i n e a r feet per minute.

3.

V i s i b l e alarms must be located so they can be r e a d i l y seen by personnel while working at the exhaust hood.

4.

A t e s t switch must be i n s t a l l e d on a l l alarms which w i l l permit the operator to v e r i f y that the l i g h t has not burned out and the sound alarm w i l l function. This t e s t must be performed while v e n t i l a t i o n system i s i n f u l l operation.

Laboratory Hood Location (Causal Factor //3): 1. Laboratory hoods must be located away from: - Heavy t r a f f i c a i s l e s - Doorways

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

222

TOXIC CHEMICAL AND EXPLOSIVES FACILITIES

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

- Adjacent walls - Crossdrafts that exceed 30 lfpm - Heating u n i t s 2.

Sidewall r e g i s t e r s and conventional c e i l i n g d i f f u s e r s s h a l l not be used f o r laboratory a i r supply.

3.

Perforated c e i l i n g panels s h a l l be used so that d i s t r i b u t i o n of supply a i r i s three feet minimum from the front face of the hood. The e x i t v e l o c i t y from these panels s h a l l not exceed 35 lfpm.

D. Laboratory Hood Performance (Causal Factor #3): 1. Laboratory hoods s h a l l have an average inward face v e l o c i t y of 100 lfpm +/- 10% with the v e l o c i t y at any point not deviating from the average face v e l o c i t y by more than 20% 2.

Leakage t e s t i n g must be done with 30 second or one minute smoke candles placed approximately 20 centimeters inside the hood. Any v i s i b l e escape of smoke should be considered i n d i c a t i v e of unacceptable performance.

3.

Laboratory hoods s h a l l be designed as deep and low i n height as p r a c t i c a l . Rough w a l l surfaces and recesses i n walls and work surfaces are unacceptable.

4.

The l o c a t i o n of sash tracks and the number of b a f f l e s and s l o t s provided are i n t e g r a l to the proper containment of materials.

5.

Laboratory hoods w i l l be equipped with a 20 centimeter l i n e taken from the face of the hood. No CSM contaminated equipment should be placed i n front of t h i s l i n e during operations.

E. Exhaust V e n t i l a t i o n / F i l t r a t i o n System (Causal Factor #5): 1. A l l laboratory exhaust a i r s h a l l be exhausted through a f i l t r a t i o n system which complies with CSL SOP 70-18. These systems have been proven to be e f f e c t i v e i n removing CSM vapor from an e x i t i n g airstream. 2.

V e n t i l a t i o n exhaust s h a l l not be r e c i r c u l a t e d .

3.

Instrumentation s h a l l be required to monitor and control the a i r f l o w through the f i l t e r system. Instrumentation s h a l l provide a means to monitor o v e r a l l pressure drop as w e l l as the pressure drop between each f i l t e r element.

4.

The f i l t e r system s h a l l include a series redundant-parallel Chemical B i o l o g i c a l R a d i o l o g i c a l (CBR) f i l t e r assembly with a c a p a b i l i t y of placing a detector between the adsorber banks to warn of "breakthrough". The system s h a l l provide a c c e s s i b i l i t y to f i l t e r s f o r r e p a i r s , maintenance and leak testing.

Scott and Doemeny; Design Considerations for Toxic Chemical and Explosives Facilities ACS Symposium Series; American Chemical Society: Washington, DC, 1987.

13.

COLLINS 5.

Designing a Chemical Surety Materiel Laboratory

223

The f i l t e r system s h a l l be as follows:

Hood - P r e f i l t e r - HEPA - Adsorber - Adsorber - HEPA - Exhaust

Downloaded by UNIV OF MASSACHUSETTS AMHERST on May 30, 2018 | https://pubs.acs.org Publication Date: July 20, 1987 | doi: 10.1021/bk-1987-0345.ch013

6.

Exhaust stacks s h a l l be designed and constructed to ensure good dispersion of exhaust a i r to the atmosphere thereby preventing r e c i r c u l a t i o n .

F. Exhaust Ductwork (Causal Factor #6): 1. A l l ductwork s h a l l be round, and welded with flange connections. 2.

Ductwork s h a l l be designed to f a c i l i t a t e dismantling and to minimize the release of contamination to adjacent areas with bagging or other approved means.

RECEIVED March 6,1987